Powered Sidewall Vent Kits
Models CF401-751 utilize a powered vent cap
which has a fan mounted inside the cap. The
powered vent cap
must
be placed on an
exterior wall. The powered sidewall vent cap
and accessories are included in a venting kit,
which
must
be furnished by Lochinvar in
accordance with CSA International requirements.
This venting kit includes the powered sidewall
fan/cap, proving switch and all necessary relays
to interlock with the water heater control system.
Models CF991-2071 utilize an inline fan, which
is positioned on the inside of the sidewall and
connected to a vent hood mounted on the
sidewall exterior. The inline fan and accessories
are included in a venting kit, which
must
be
furnished by Lochinvar in accordance with CSA
International requirements.
This venting kit includes the inline fan, exterior
vent hood, a tapered vent adapter, barometric
damper, proving switch and all necessary relays
to interlock with the water heater control system.
The connection from the vent to the sidewall
fan/powered vent cap
must
be made with
listed Type “B” double wall (or equivalent) vent
and accessories. The installer supplies this vent
pipe material.
For models CF401-751, maximum total
equivalent length of the vent pipe cannot
exceed 50 equivalent feet (15.24m).
Models CF991-2071 allow a maximum
total equivalent length of 100 feet (30.48m).
Subtract 5 feet (1.52m) for each elbow in the
vent.
Power DirectAire
®
Horizontal
This vent system requires the installation of
two vent pipes directly to the unit, one pipe
for flue products and one for combustion air.
Both vent pipes are installed horizontally with
a sidewall termination point. The vent
connection is made directly to the top of the unit
and utilizes either the powered vent cap or inline
fan as described in the side wall venting section
(Pages 10-11).
L o c h i n v a r
D E S I G N E R
’
S
G U I D E
C O P P E R
-
F I N
I I
W A T E R
H E A T E R
6 1 5 - 8 8 9 - 8 9 0 0
1 1
(TABLE D) POWERED SIDEWALL VENT KIT PART NUMBERS
MODEL
FLUE SIZE*
SIDEWALL VENT
NUMBER
CAP KIT
CF401
6
”
SVK3006
CF501
6
”
SVK3006
CF651
8
”
SVK3008
CF751
8
”
SVK3008
CF991
10
”
SVK3009
CF1261
12
”
SVK3010
CF1441
12
”
SVK3010
CF1801
14
”
SVK3012
CF2071
14
”
SVK3012
(FIG. 11) POWER DIRECTAIRE
®
HORIZONTAL
(POWERED VENT CAP SHOWN)
3’
12”