The indoor units
must
be installed so that
the ignition system components are
protected from water (dripping, spraying,
rain, etc.) during appliance operation and
service (circulator replacement, control
replacement, etc.).
The appliance
must
be installed
on a level, non-combustible floor.
Concrete over wood is not considered a
non-combustible floor. Maintain required
clearances from combustible surfaces.
For installation on a combustible
floor only when installed on
special base:
Units installed over a
combustible floor
MUST
use the Special
Combustible Floor Base. The unit
must
be
centered on the base as shown in FIG. 1.
• Provide a base of hollow clay tile or
concrete blocks from 8
”
to 12
”
thick
and extending 24
”
beyond the sides.
• The blocks
must
be placed in line so
that the holes line up horizontally to
provide a clear passage through the
blocks.
•
This procedure should also be
followed if electrical conduit or
radiant heat distribution piping
runs through the floor and
beneath the appliance.
• Ensure that combustible floor base
meets local fire code requirements.
• The correct kit number for the required base
is noted on the rating plate of each unit
and listed in Table A.
2.
3.
4.
L o c h i n v a r
D E S I G N E R
’
S
G U I D E
C O P P E R
-
F I N
I I
W A T E R
H E A T E R
6 1 5 - 8 8 9 - 8 9 0 0
3
(FIG. 1) CF 991-2071 REQUIREMENTS FOR
INSTALLATION OVER COMBUSTIBLE FLOOR
(TABLE A)
COMBUSTIBLE FLOOR KITS
MODEL NUMBER
KIT NUMBER
CF401
CFK3301
CF501
CFK3302
CF651
CFK3303
CF751
CFK3304
Under no circumstances is the
manufacturer to be held responsible
for water damage in connection
with this unit or any of its
components.