PIPING DIAGRAM
TWO HEATERS-SINGLE TANK
FULL PORT
BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE
ELBOW
UNION
EXPANSION
TANK
CHECK
VALVE
THERMOMETER
REDUCING
TEE
REDUCING
TEE
L E G E N D
LOCHINVAR
WATER HEATER
INLET
INLET
OUTLET
OUTLET
BUILDING RETURN
DRAIN
LOCK-TEMP
STORAGE TANK
COLD WATER
SUPPLY
BUILDING
HOT WATER
SUPPLY
LIT0138
RELIEF
VALVE
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION
Pipe sizing chart provides minimum pipe size for common manifold piping to insure adequate flow.
NUMBER OF
COMMON MANIFOLD SIZE
NUMBER OF
COMMON MANIFOLD SIZE
UNITS
(Min.)
UNITS
(Min.)
CF 401 thru 751
CF 991 thru 2071
1
2
”
1
2
1
/
2
”
2
3
”
2
4
”
3
3
1
/
2
”
3
4
”
4
4
”
4
5
”
5
5
”
5
6
”
6
5
”
6
6
”
L o c h i n v a r
D E S I G N E R
’
S
G U I D E
C O P P E R
-
F I N
I I
W A T E R
H E A T E R
615 - 8 8 9 - 8 9 0 0
A4
This illustration is for concept only and should not be used for any actual installation without engineering
or technical advice from a licensed engineer. All necessary equipment may not be illustrated.
Gray shaded area represents common manifold piping.