Installation
32
Instruction manual CH
3
is
Adjusting the pressure
1. Remove the cap (2) from the burner pressure regulator.
2. Depending on the correction required, correct the burner pressure by turning
adjustment screw (3):
-
Adjustment screw anticlockwise: burner pressure decreases.
-
Adjustment screw clockwise: burner pressure increases.
3. Cover the opening of the adjusting screw and check the burner pressure
against the value given in thegas data table
(3.4.3 "Gas data")
.
4. If the pressure reading is not correct, repeat the burner pressure adjustment
until the correct pressure is reached.
5. Fit the cap (2) back on the burner pressure regulator.
Finalising
1. Shut off the gas supply.
2. Disconnect the two pressure gauges and retighten the sealing screws in the
test nipples.
3. Replace the cover.
Содержание CH 100 CE
Страница 4: ...4 Instruction manual CH gis...
Страница 10: ...Introduction 10 Instruction manual CH 1 gis...
Страница 16: ...Working principle of the water heater 16 Instruction manual CH 2 gis...
Страница 36: ...Conversion to a different gas category 36 Instruction manual CH 4 is...
Страница 44: ...Status of the water heater 44 Instruction manual CH 8 gis...
Страница 46: ...Starting the water heater 46 Instruction manual CH 9 gis...
Страница 48: ...Shutting down 48 Instruction manual CH 10 gis...
Страница 60: ...Electrical diagram 60 Instruction manual CH 14 is 1 brown 2 blue 3 yellow green 4 black 5 white 0305906 R0...
Страница 62: ...Electrical diagram 62 Instruction manual CH 14 is...
Страница 64: ...Declaration of Conformity 64 Instruction manual CH 15 is...
Страница 66: ...0310 570 1 0 UK Index Instruction manual CH...