Installation
24
Instruction manual CH
3
is
3.6
Unvented water
connections
Warning
The installation should be carried out by a competent person, in compliance
with general and locally applicable regulations
(1.3 "Regulations")
.
3.6.1
Cold water side
See (A) in the installation diagram
(3.5 "Installation diagram")
.
1. Fit an approved stop valve (4) on the cold water side as required by the
applicable regulations
(1.3 "Regulations")
.
2. The maximum working pressure of the water heater is 8 bar. Because the
pressure in the water pipe at times can exceed 8 bar, you must fit an
approved pressure-reducing valve (1).
3. Fit a non-return valve (5) and an expansion vessel (16).
4. Fit an expansion valve (15) and connect the overflow side to an open waste
water pipe.
3.6.2
Shunt pipe
You can connect a top to bottom circulation pump to prevent stacking of the
water in the water heater.
1. Optional: Depending on the draw-off pattern, fit a shunt pipe (Ø 22 mm), a
stop valve (11) and a top-to-bottom circulation pump (7).
2. Fit a non-return valve (5).
3. Fit a stop valve (11).
3.6.3
Hot water side
See (B) in the installation diagram
(3.5 "Installation diagram")
.
Note
Insulating long hot water pipes prevents unnecessary energy loss.
1. Optional: fit a temperature gauge (12) so you can check the temperature of
the tap water.
2. Fit the T&P valve (3).
3. Fit a stop valve (11) in the hot water outlet pipe for servicing.
3.6.4
Drain valve
1. Fit the standard drain valve supplied (9).
2. If desired, fit a circulation pipe
(3.6.5 "Circulation pipe")
.
Otherwise, fit the sealing nut and gasket (C) supplied with the drain valve,
as per the diagram.
Содержание CH 100 CE
Страница 4: ...4 Instruction manual CH gis...
Страница 10: ...Introduction 10 Instruction manual CH 1 gis...
Страница 16: ...Working principle of the water heater 16 Instruction manual CH 2 gis...
Страница 36: ...Conversion to a different gas category 36 Instruction manual CH 4 is...
Страница 44: ...Status of the water heater 44 Instruction manual CH 8 gis...
Страница 46: ...Starting the water heater 46 Instruction manual CH 9 gis...
Страница 48: ...Shutting down 48 Instruction manual CH 10 gis...
Страница 60: ...Electrical diagram 60 Instruction manual CH 14 is 1 brown 2 blue 3 yellow green 4 black 5 white 0305906 R0...
Страница 62: ...Electrical diagram 62 Instruction manual CH 14 is...
Страница 64: ...Declaration of Conformity 64 Instruction manual CH 15 is...
Страница 66: ...0310 570 1 0 UK Index Instruction manual CH...