Instruction manual CH
31
is
Reading off and adjusting
1. Isolate the appliance from the mains power
(10.3 "Isolating the appliance
from the mains")
.
2. To check the supply pressure, test nipple (6) is used. The manifold test
nipple (8) is used for measuring the burner pressure.
Sealing screws are located inside the test nipples. Loosen both sealing
screws by a few turns. Do not completely loosen them; they can be difficult
to retighten.
3. Connect a pressure gauge to the manifold test nipple (8).
4. Open the gas supply and bleed the air from the mains gas supply via test
nipple (6).
5. Connect a pressure gauge to the manifold test nipple (6) when gas starts to
flow from this nipple.
6. Switch on the power to the appliance using the isolator on the appliance.
7. Set the control thermostat to the maximum temperature and start the
appliance running by setting the ON/OFF switch to position I.
8. The heating cycle will start, and after a short time the burner tray will ignite.
9. After the burner tray has ignited, wait approximately 1 minute before reading
the dynamic pressures.
Note
If the burner pressure is not correct and the appliance is fitted with a blank
plate or high-low control, you will
not be able to adjust
the pressure. In this
case, consult your installation engineer or supplier. If the appliance is indeed
fitted with a burner pressure regulator, the pressure can be adjusted
( "Adjusting
the pressure")
.
10. Adjust the burner pressure by turning the adjusting screw (10), depending
on the correction required:
-
Adjustment screw anticlockwise: burner pressure decreases.
-
Adjustment screw clockwise: burner pressure increases.
11. Cover the opening of the adjusting screw and check the burner pressure
against the value given in the gas data table
(3.4.3 "Gas data")
.
12. If the pressure reading is not correct, repeat the burner pressure adjustment
until the correct pressure is reached.
13. Fit the cap (9) back on the burner pressure regulator.
14. Shut off the gas supply.
15. Disconnect the two pressure gauges and retighten the sealing screws in the
test nipples.
Note
Before starting the appliance up, take time to fill in the warranty card
supplied with the appliance. This enables us to guarantee the quality of our
systems and further enhance our warranty procedure.
16. Please return this card as soon as possible. Your customer will then receive
a warranty certificate with our warranty conditions.
Содержание CH 100 CE
Страница 4: ...4 Instruction manual CH gis...
Страница 10: ...Introduction 10 Instruction manual CH 1 gis...
Страница 16: ...Working principle of the water heater 16 Instruction manual CH 2 gis...
Страница 36: ...Conversion to a different gas category 36 Instruction manual CH 4 is...
Страница 44: ...Status of the water heater 44 Instruction manual CH 8 gis...
Страница 46: ...Starting the water heater 46 Instruction manual CH 9 gis...
Страница 48: ...Shutting down 48 Instruction manual CH 10 gis...
Страница 60: ...Electrical diagram 60 Instruction manual CH 14 is 1 brown 2 blue 3 yellow green 4 black 5 white 0305906 R0...
Страница 62: ...Electrical diagram 62 Instruction manual CH 14 is...
Страница 64: ...Declaration of Conformity 64 Instruction manual CH 15 is...
Страница 66: ...0310 570 1 0 UK Index Instruction manual CH...