background image

These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment.

IMPORTANT INFORMATION

0310570
March 2012

Installation, Commissioning, User & Maintenance Instructions

High Efficiency Water Heaters and Boilers

Charger

Direct Gas Fired Floor Standing Water Heater

with Permanent Pilot Ignition

Models:

CH 100 G CE
CH 155 G CE
CH

and PG CE
and PG CE

200 G CE and PG CE

CH 300 G CE and PG CE
CH 400 G CE and PG CE
CH 500 G CE and PG CE
CH 600 G CE and PG CE

Содержание CH 100 CE

Страница 1: ...ch 2012 Installation Commissioning User Maintenance Instructions High Efficiency Water Heaters and Boilers Charger Direct Gas Fired Floor Standing Water Heater with Permanent Pilot Ignition Models CH...

Страница 2: ...Lochinvar Ltd 7 Lombard Way The MXL Centre Banbury Oxon OX16 4TJ www lochinvar ltd uk High Efficiency Water Heaters and Boilers Tel 44 0 1295 269 981 Fax 44 0 1295 271 640 Email info lochinvar ltd uk...

Страница 3: ...s Liability The supplier accepts no liability for claims from third parties arising from unauthorised use use other than that stated in this manual and use other than in accordance with the General Co...

Страница 4: ...4 Instruction manual CH gis...

Страница 5: ...ons 19 3 5 Installation diagram 23 3 6 Unvented water connections 24 3 7 Vented water connections 25 3 8 Gas connection 27 3 9 Flue gas discharge 27 3 10 Electrical connection 28 3 11 Checking the sup...

Страница 6: ...s 49 11 1 Introduction 49 11 2 Troubleshooting table for general errors 50 11 3 Troubleshooting table no hot water 51 11 4 CH Troubleshooting table insufficient hot water 52 12 Performing maintenance...

Страница 7: ...hat to do if you smell gas Warning If you smell gas No naked flames No smoking Avoid causing sparks Do not use any electrical equipment or switch i e no telephones plugs or bells Open windows and door...

Страница 8: ...is water heater is not intended to be used by children Always supervise children and ensure that they do not play with the water heater 1 5 Maintenance A service should be carried out at least once a...

Страница 9: ...chapter describes how to fill the water heater Draining This chapter describes how to drain the water heater The control panel This chapter describes the appliance s control panel and how to use it S...

Страница 10: ...Introduction 10 Instruction manual CH 1 gis...

Страница 11: ...l panel 8 combustion chamber 9 anode 10 tank 11 heat exchanger 12 inspection and cleaning opening 14 cold water inlet 15 drain valve 16 gas control valve 21 flame probe 22 chimney pipe 24 insulation l...

Страница 12: ...on of gas into the burner bars also draws in the primary air required for combustion The narrow opening in the orifice causes the gas flow to accelerate This in turn causes a partial vacuum It is this...

Страница 13: ...he gas supply to the burner tray and which is switched via the I 0 II switch circuit and the control high limit and flue gas thermostats This circuit is powered by the supply voltage 2 The safety valv...

Страница 14: ...the enamelled coating in the appliance or to the tank A non return valve prevents excessive pressure buildup in the water supply system This valve also prevents water from flowing backwards from the t...

Страница 15: ...the water temperature at the top of the tank If the pressure in the tank becomes excessive 10 bar or the water temperature is too high 97 C the valve will open The hot water can now flow out of the t...

Страница 16: ...Working principle of the water heater 16 Instruction manual CH 2 gis...

Страница 17: ...before the appliance may be started up 9 Starting the water heater in particular Packaging Ambient conditions Technical specifications Vented water connections Vented water connections Gas connection...

Страница 18: ...iler room They are type B11BS 3 3 1 Air humidity and ambient temperature The boiler room must be frost free or be protected against frost The table shows the ambient conditions that must be adhered to...

Страница 19: ...le clearance is less than 100 cm flexible magnesium anodes may be ordered Note When installing the appliance be aware that any leakage from the tank and or connections can cause damage to the immediat...

Страница 20: ...k the dimensions 3 4 Technical specifications gas data 3 4 3 Gas data and other specifications 3 4 2 General and electrical specifications of any accessories you plan to use 3 4 1 Dimensions of the wa...

Страница 21: ...5 1600 1 Cold water supply connection external R11 2 R11 2 R11 2 R11 2 R11 2 R11 2 R11 2 2 Hot water outlet connection internal Rp11 2 Rp11 2 Rp11 2 Rp11 2 Rp11 2 Rp11 2 Rp11 2 3 Gas control connectio...

Страница 22: ...50 1 70 1 75 1 Blank plate 2 Burner pressure regulator 3 High low regulator 1 2 or 3 1 1 1 1 1 1 1 G30 30 mbar butane Nominal load gross calorific value kW 33 9 42 2 53 4 59 2 80 8 100 1 127 5 Nominal...

Страница 23: ...ry 4 stop valve recommended 5 non return valve mandatory 6 circulation pump optional 7 top to bottom circulation pump optional 9 drain valve 10 manual gas valve mandatory 11 service stop valve mandato...

Страница 24: ...nnect the overflow side to an open waste water pipe 3 6 2 Shunt pipe You can connect a top to bottom circulation pump to prevent stacking of the water in the water heater 1 Optional Depending on the d...

Страница 25: ...ve 9 as per the drain valve diagram 3 6 4 Drain valve 3 7 Vented water connections Warning The installation should be carried out by a competent person in compliance with general and locally applicabl...

Страница 26: ...fit a circulation pipe 3 6 5 Circulation pipe Otherwise fit the sealing nut and gasket C supplied with the drain valve as per the diagram 3 7 5 Circulation pipe See C in the installation diagram 3 5...

Страница 27: ...pply pipe 2 Blow the gas pipe clean before use 3 Close the manual gas valve 4 Fit the gas supply pipe to the gas control valve Warning After fitting check for leaks 3 9 Flue gas discharge Warning The...

Страница 28: ...he installation should be carried out by a competent person in compliance with general and locally applicable regulations 1 3 Regulations 3 10 1 Introduction Topics covered in this paragraph in sequen...

Страница 29: ...ed until you are ready to commission it 1 Feed the power cable through the metric strain relief in the top of the control column 2 Connect the earth live L1 and neutral N of the power cable to termina...

Страница 30: ...r the first time or after conversion you must always check the supply pressure and burner pressure Note The easiest way to check the gas pressures is by using two pressure gauges This procedure assume...

Страница 31: ...is not correct and the appliance is fitted with a blank plate or high low control you will not be able to adjust the pressure In this case consult your installation engineer or supplier If the applia...

Страница 32: ...w clockwise burner pressure increases 3 Cover the opening of the adjusting screw and check the burner pressure against the value given in thegas data table 3 4 3 Gas data 4 If the pressure reading is...

Страница 33: ...gases liquid petroleum gas or natural gas or other gas category other than that for which the appliance has been configured at the factory then the appliance will have be adapted using a special conv...

Страница 34: ...the radiation shield condensation tray was loosened re fasten it 11 Check whether there is a burner pressure regulator 1 attached to the gas control or simply a blank plate 5 Note If the supply press...

Страница 35: ...35 is Legend Unused numbers are not applicable 4 burner pressure controller 5 blank plate 6 supply pressure nipple 7 gas control 8 manifold test nipple 9 sealing screw 10 burner pressure adjustment sc...

Страница 36: ...Conversion to a different gas category 36 Instruction manual CH 4 is...

Страница 37: ...pump optional 7 top to bottom circulation pump optional 9 drain valve 10 manual gas valve mandatory 11 service stop valve mandatory 12 temperature gauge recommended 14 draw off points 15 expansion val...

Страница 38: ...is defective or incorrectly fitted The water supply pressure is greater than the specified 8 bar Rectify this by fitting a pressure reducing valve 1 The expansion valve in the protected cold supply se...

Страница 39: ...pump optional 7 top to bottom circulation pump optional 9 drain valve 10 manual gas valve mandatory 11 service stop valve mandatory 12 temperature gauge recommended 14 draw off points 15 expansion val...

Страница 40: ...ater supply A 6 Open the drain valve 9 7 Bleed the appliance or installation so that it drains completely 6 2 Draining vented installations Some service activities require the water heater to be drain...

Страница 41: ...ode position 0 or the weekly program mode position II See Operating modes The appliance remains live even when in the OFF mode This ensures that the frost protection remains activated Note To isolate...

Страница 42: ...for fine setting turn the large hand clockwise until the current time is set The manual switch 4 must always be in the central position this activates the timer program 7 7 Flue gas thermostat reset...

Страница 43: ...if the Power Anode is not working off this will have no effect on the hot water supply 8 4 Error conditions If the appliance has an error heat demand will be temporarily ignored There are various type...

Страница 44: ...Status of the water heater 44 Instruction manual CH 8 gis...

Страница 45: ...cycle 9 3 The appliance s heating cycle Warning If the pilot flame goes out during the heating cycle or ignition procedure you must wait 5 minutes before repeating the ignition procedure 9 3 The appli...

Страница 46: ...Starting the water heater 46 Instruction manual CH 9 gis...

Страница 47: ...s power in the correct way The correct procedure is as follows 1 Shut down the appliance by putting the ON OFF switch to position 0 2 Isolate the appliance from the power supply by setting the isolato...

Страница 48: ...Shutting down 48 Instruction manual CH 10 gis...

Страница 49: ...ruction manual CH 49 gis 11 Errors 11 1 Introduction This chapter covers the following errors Gas smell Water leakage Explosive ignition Poor flame profile Power Anode No hot water Insufficient hot wa...

Страница 50: ...tallation engineer Leakage from another nearby water water heater or pipe segment Trace the leak Leakage from the water heater tank Consult the supplier and or manufacturer Condensation Before drawing...

Страница 51: ...No supply voltage present 1 Check whether the isolator is ON 2 Check whether there is power to the isolator The measured voltage must be 230 VAC 15 10 If ignition is not improved consult your installa...

Страница 52: ...ol thermostat to a higher value Hot water supply is used up 1 Reduce hot water consumption and give the water heater time to heat up 2 If this error persists check whether the high limit thermostat is...

Страница 53: ...ure and adjust them if necessary 6 Also check that this is running properly during the The appliance s heating cycle 7 Check that all components of the chimney flue system are properly attached 8 Test...

Страница 54: ...lime build up prevent effective conduction of the heat to the water Periodic cleaning and descaling prevents build up of these deposits This increases the service life of the water heater and also im...

Страница 55: ...lts in the sequence shown in the diagram 12 4 Gas side maintenance 12 4 1 Introduction The following steps must be carried out on the gas side 1 Clean the burner s 2 Clean the orifice s 3 Checking the...

Страница 56: ...maintenance 56 Instruction manual CH 12 s 12 5 Finalising maintenance To finalise the maintenance carry out the following steps 1 Fill the appliance 5 Filling 2 Start the appliance up 9 Starting the w...

Страница 57: ...ce with any relevant requirements of the local gas distributor and local authority b The water heater remains installed at the original site of installation c The water heater is used exclusively with...

Страница 58: ...anty are limited to free delivery from the warehouse of the replacement assemblies parts or water heater respectively Labor installation and any other costs associated with the replacement will not be...

Страница 59: ...Instruction manual CH 59 is 14 Electrical diagram 14 1 Introduction This chapter shows the electrical diagram s and accompanying legend...

Страница 60: ...Electrical diagram 60 Instruction manual CH 14 is 1 brown 2 blue 3 yellow green 4 black 5 white 0305906 R0...

Страница 61: ...lux safeguard L2 Phase input of controller COMPONENTS A ON OFF switch B Control thermostat C High limit thermostat D Safety thermostat E Gas control F Eye terminal for earthing to the Jacket G Thermal...

Страница 62: ...Electrical diagram 62 Instruction manual CH 14 is...

Страница 63: ...55014 1 1993 EN55014 2 1997 EN61000 3 2 1995 EN61000 3 3 1995 EN50165 1997 M arch 1 20 12 EEC Declaration of Conformity Supplier hereby declares that the following products Product description Product...

Страница 64: ...Declaration of Conformity 64 Instruction manual CH 15 is...

Страница 65: ...ty 18 I installation diagram 23 installation engineer 8 9 isolator 29 J join circulation pipe 25 26 cold water side 24 25 electrical 28 29 gas 27 hot water side 24 shuntleiding 24 25 L liability 3 M m...

Страница 66: ...0310 570 1 0 UK Index Instruction manual CH...

Отзывы: