OPERATIONAL CHECKLIST

This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job 

troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper 

piping and wiring can result in unsatisfactory system performance, it is suggested that the installation be examined before using the 

checklist.  Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.

The system should be filled with water, purged of air, valves properly set and utilities connected and ready to operate

.

   

 

                                                   

REMEDY

  COMPLAINT 

                CAUSE 

                     USER 

                     SERVICEMAN

*Water not hot enough. 

Thermostat set too low. 

Set thermostat dial to a higher

  

 

temperature.

   

Thermostat out of calibration. 

Call serviceman 

Recalibrate thermostat. If thermostat cannot

   

 

 

be recalibrated, replace.

*Insufficient hot water 

Thermostat set too low. 

Set thermostat dial to a higher

*See WATER TEMPERATURE   

temperature.

CONTROL WARNING (on 

Page 20). 

Thermostat out of calibration. 

Call serviceman. 

Recalibrate thermostat. If thermostat cannot

   

 

 

be recalibrated, replace.

   

Main manual gas shutoff 

Open main manual gas shutoff 

   

valve partially closed. 

valve to fullest extent. 

 

   

Heater too small for demand. 

Space usage to give heater time

   

 

to restore water temperature. 

 

   

Thermostat differential is 

Call serviceman. 

Replace dual bulb controller if differential is

   

too wide. 

 

greater than 4°F.

   

Heater recovery is slower. 

Call serviceman. 

Check gas input. If incorrect, adjust gas

   

 

 

pressure or replace main burner orifice.

   

Drafthood not installed or 

Call serviceman. 

Install drafthood or baffles as furnished 

   

one or more flue baffles. 

 

with unit.

Water temperature too hot. 

Thermostat set too high. 

Set thermostat to a lower setting. 

Heater makes sounds: sizzling.  Condensation on outside

   

of tank, normal. 

 

 

Rumbling. 

Sediment accumulation on 

Drain a quantity of water through 

Delime heater.

   

bottom of tank. 

drain valve. If rumbling persists,

   

 

call a serviceman.

Ticking or metallic sounds. 

Expansion and contraction- 

   

normal.

Pounding. 

Air chambers in piping have 

Drain piping system and refill.

   

become waterlogged. 

Heater must be off while this is

   

 

being done.

Combustion noises. 

Too much primary air. 

Adjust shutters. 

   

Overfired heater; Incorrect 

Call serviceman. 

Check and correct as necessary.

   

burners or orifice for type

   

of gas used.

Water leaks. 

Drain valve not closed 

If drain valve cannot be closed

   

 tightly. 

tightly, replace.

   

If leakage source cannot 

Shut off gas supply to heater 

Repair or in case of suspected tank leakage,

   

be corrected or identified, 

and close cold water inlet valve 

be certain to confirm before replacing heater.

   

call serviceman. 

to heater.

Gas odors. 

Heater is overfired. 

Shut off gas supply to heater 

Check for sooted flue passage.

   

 

and call a serviceman.

   

 

 

Check for obstructed vent line.

   

 

 

Check backdraft or lack of draft.

   

Possible gas leaks. 

Shut off gas supply to heater and

   

 

call gas company at once.

  

 

Содержание CGL150

Страница 1: ...ed in U S A 1011 322880 000 CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THIS APPLIANCE Thank you for b...

Страница 2: ...installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available from the National Fire Protection...

Страница 3: ...ater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTIC AND OR EXHAUST FANS OPERATING ON THE PREMISES WITHAWATER HEATER...

Страница 4: ...n per cubic foot of air Therefore the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply Failure to make this reduction would result in an...

Страница 5: ...DUCER BLOWER ASSEMBLY All units are equipped with a exhaust inducer The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by products int...

Страница 6: ...ns above 2000 feet 610m refer to HIGH ALTITUDE INSTALLATIONS section of this manual for input reduction procedure LEVELING If the unit is not level insert the bolts which were used in crating into the...

Страница 7: ...ater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heaters This water heater...

Страница 8: ...r well Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device...

Страница 9: ...ALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIMENT TRAPORDRIPLEG MUSTBEINCORPORATEDINTHEPIPING SEE FIG 9 THE DIRT LEG...

Страница 10: ...h the latest version of the National Electrical Code ANSI NFPA No 70 FIGURE 10 SINGLE UNIT WIRING DIAGRAM must conform to all local code authority having jurisdiction AN ELECTRICAL GROUND IS REQUIRED...

Страница 11: ...emperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the te...

Страница 12: ...LD NOT EXCEED SAFE USE TEMPERATUREAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Страница 13: ...BE CLOSED ON DURING THE RINSE OPERATION AND OPEN OFF WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Страница 14: ...in the installation diagrams on the following pages are typical The discharge opening of the temperature and pressure relief valve must be piped to an open drain and should not be subject HEATER WITH...

Страница 15: ...NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LI...

Страница 16: ...RS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEA...

Страница 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN LOCHINVAR T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 18: ...rner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or the uni...

Страница 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Страница 20: ...WHICH INJURYOCCURS VARIES WITH THE PERSON S AGE AND TIME OF EXPOSURE THE SLOWER RESPONSETIMEOFCHILDREN AGEDORDISABLEDPERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDRENTOUSEAHOTWATERTAP...

Страница 21: ...essure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure gauge and replace...

Страница 22: ...when removed New pipe collars will insure that the seal is such as to prevent leakage of flue products when properly installed NOTE Anode rod inspection may need to be made more frequently in areas s...

Страница 23: ...calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing Check that main manual gas shutoff valve is fully open...

Страница 24: ...e complete model and serial number as it appears on the product Refer to the part s list for more information SERVICE The installer may be able to observe and correct certain problems which may arise...

Страница 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Страница 26: ...n Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dr...

Страница 27: ...so installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited...

Страница 28: ...28 Copyright 2011 Lochinvar LLC All rights reserved 300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Service email 2tech lochinvar com www Lochinvar com...

Отзывы: