2  

Maintenance

Service Manual

17

2  

Maintenance 

(continued)

Follow the service and maintenance procedures given throughout this manual and in component literature
shipped with the water heater.  Failure to perform the service and maintenance could result in damage to
the water heater or system.  Failure to follow the directions in this manual and component literature could
result in severe personal injury, death, or substantial property damage.

The water heater should be inspected annually only by a qualified service technician.  In addition, the
maintenance and care of the water heater designated in Table 2A and explained on the following pages must
be performed to assure maximum water heater efficiency and reliability.  Failure to service and maintain the
water heater and system could result in equipment failure.

Electrical shock hazard – Turn off power to the water heater before any service operation on the water heater
except as noted otherwise in this instruction manual.  Failure to turn off electrical power could result in
electrical shock, causing severe personal injury or death.

Address reported problems

1.

Inspect any problems reported by the owner and
correct before proceeding.

Inspect water heater area

1.

Verify that water heater area is free of any combustible
materials, gasoline and other flammable vapors and
liquids.

2.

Verify that air intake area is free of any of the
contaminants listed in Section 1 of the Armor Water
Heater Installation and Operation Manual.  If any of
these are present in the water heater intake air vicinity,
they must be removed.  If they cannot be removed,
reinstall the air and vent lines per this manual and the
Armor Water Heater Installation and Operation
Manual.

Inspect water heater interior

1.

Remove the front access cover and inspect the interior
of the water heater.

2.

Vacuum any sediment from inside the water heater and
components.  Remove any obstructions.

Clean condensate trap

1.

Inspect the condensate drain line, condensate PVC
fittings, and condensate trap.

2.

Remove the PVC cap retaining screw from the PVC cap
(FIG. 2-1).

3.

Remove the 2 inch PVC cap with the switch located at
the top of the trap (FIG. 2-1).

4.

Remove any sediment in the trap.

5.

Fill with fresh water until the water begins to pour out
of the drain.

6.

Replace the cap.  Press the cap onto the trap until the
cap makes contact with the drain.

7.

Replace the retaining screw.

Eliminate all system or water heater leaks.
Leaking water may cause severe property
damage.

1.

Inspect all water and gas piping and verify to be leak free.

2.

Look for signs of leaking lines and correct any problems
found.

3.

Check gas line using the procedure found in Section 7 -  Gas
Connections of the Armor Water Heater Installation and
Operation Manual.

Check all piping for leaks

The condensate trap must be filled with
water during all times of water heater
operation to avoid flue gas emission from the
condensate drain line.  Failure to fill the trap
could result in severe personal injury or
death.

WARNING

WARNING

WARNING

WARNING

WARNING

PVC TEE ASSEMBLY

(FACTORY SUPPLIED)

TO FLOOR

DRAIN

2” PVC CAP WITH

BLOCKED DRAIN SWITCH

RETAINING

SCREW

CONDENSATE FROM

HEAT EXCHANGER

Figure 2-1

Condensate Trap

Содержание ARMOR 150

Страница 1: ...n Read all instructions including this manual and the Armor Water Heater Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe p...

Страница 2: ...ntenance that are important but not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing wate...

Страница 3: ...when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines Avoid breathing dust and contact with skin and eyes Use NIOSH certified dust respira...

Страница 4: ...ation Armor water heater operation A General C Data Logging D Functions E WHR Settings H Control Modes I Circulation Pumps J Service Notification Maintenance Service and maintenance schedules Address...

Страница 5: ...1 Service Service Manual 5 The Armor water heater display...

Страница 6: ...ER BUILDING MANAGEMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE SENSOR FLUE GAS SENSOR HIGH LIMIT SENSOR FLAME SENSOR LOW WATER CUTOFF OPTIONAL BLOCKED DRAIN SWI...

Страница 7: ...GE CONNECTION BOARD SMART SYSTEM CONTROL BOARD ALARM BELL AUX DEVICE RELAY RUNTIME CONTACTS SEQUENCER BUILDING MANAGEMENT SYSTEM DHW PUMP IGNITER BLOWER GAS VALVE DISPLAY PANEL PC INTERFACE Control ou...

Страница 8: ...nces of operation for water heating operation Access modes User The user can adjust water heating set point using the UP and DOWN buttons at any time during normal operation By entering the USER code...

Страница 9: ...nce the prepurge cycle is complete and the blocked drain switch is closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve W...

Страница 10: ...to toggle menu listing DOWN If the code is entered incorrectly the display will return to its previous mode You will have to start over at step 1 to enter the code COMMENTS Digit shown underlined at...

Страница 11: ...l flash H3 Cascade Addr H3 will flash H3 Cascade Addr H2 will stop flashing parameter value will appear H3 Cascade Addr UP or DOWN Parameter will increase or decrease depending on button pressed H3 Ca...

Страница 12: ...o No Yes Yes DATA FUNCTIONS E 3 Tank Set Point 14 Yes Yes Yes Yes LOGGING WHR SETTINGS The parameters for Building Management System operation are not listed in this table They are only accessible usi...

Страница 13: ...nternal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for water heating This feature is only used when a tank sensor is used This pa...

Страница 14: ...ddresses must be different for each Member The addresses can be in any order regardless of the order in which the units are wired together This parameter is adjustable by the installer by accessing pa...

Страница 15: ...rol determines that a scheduled service is due based on the hours of actual operation the water heater display will alternate the standard water heater display text with the message SERVICE DUE every...

Страница 16: ...up checkout and performance verification per Section 10 in the Armor Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat ex...

Страница 17: ...these are present in the water heater intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lines per this manual and the Armor Water Heater Installation and O...

Страница 18: ...ter Heater Installation and Operation Manual before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspe...

Страница 19: ...d securely attached Check control settings 1 Set the SMART SYSTEM control module display to Parameter Mode and check all settings See Section 1 of this manual Adjust settings if necessary See Section...

Страница 20: ...ance instructions for the water heater in Section 10 Startup of the Installation and Operation Manual Do not drain the water heater unless it will be exposed to freezing temperatures If using freeze p...

Страница 21: ...mum 4 inches w c natural 8 inches w c LP with gas flowing verify during water heater startup Check control module fuses ALWAYS check control module fuses before replacing control module or any major c...

Страница 22: ...ontrol board Blown fuse Replace fuse F3 on the main control board see page 21 of this manual No Burner Operation Main control board temperature set point satisfied Review temperature setting Remote th...

Страница 23: ...F Resistance Temperature F Resistance 68 14 773 176 1 707 86 9 804 194 1 266 104 6 652 212 952 122 4 607 230 726 140 3 252 248 560 158 2 337 Checking temperature sensors The water heater temperature s...

Страница 24: ...water pressure Verify system pressure is a minimum of 12 PSI No Pump Operation Blown fuse Replace fuse F5 on the control board see page 21 of this manual Faulty pump Replace pump Faulty pump relay Re...

Страница 25: ...ck for loose or misplaced jumpers if flow switch is not installed Blown fuse Replace fuse F2 on the control board see page 21 of this manual Blocked Drain SW will require a manual reset once condition...

Страница 26: ...ted and is not damaged Verify that the vent air intake pipes are correctly installed and that there are no obstructions Check for 24 VAC to the gas valve at the 2 pin connection on the side of the mai...

Страница 27: ...ir inlet is connected and is not damaged Verify that the vent air intake pipes are installed correctly and there are no obstructions Check for 24 VAC to the gas valve at the 2 pin connection on the si...

Страница 28: ...e condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The actual fan RPM is 30 lower than what is being called for Vent air intake lengths exceed the maximum allow...

Страница 29: ...page 23 of this manual Replace the sensor if necessary Sensor Shorted will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset Eit...

Страница 30: ...mor Water Heater Installation and Operation Manual for water heater pump specifications Outlet water temperature has exceeded the maximum outlet water temperature Verify that the system is full of wat...

Страница 31: ...e main control board if necessary If 120 VAC is present on a call for heat and the water heater pump is not operating replace the pump Verify that the water heater pump is set to the proper speed or t...

Страница 32: ...Table 3F Troubleshooting Chart Combustion Levels POSSIBLE CAUSE CORRECTIVE ACTION Vent Air Intake Length or Obstruction Refer to Section 3 General Venting of the Armor Water Heater Installation and O...

Страница 33: ...four 4 adjustments and the combustion is still not within the specified range revisit the possible causes in Table 3F on page 32 or replace the gas valve Figure 3 2 Gas Valve Adjustment Models 150 285...

Страница 34: ...gas valve Figure 3 4 Gas Valve Adjustment Model 500 Service Manual 3 Troubleshooting continued Models 600 800 Locate the throttle adjustment screw on top of the gas valve see FIG 3 4 Using an Allen w...

Страница 35: ...35 NOTES...

Страница 36: ...ns in vent terminations and safety shutoff testing and instructions Revision E ECO C02738 reflects the addition of the Gas Valve Adjustment Procedure for a 399 model on page 33 Revision F ECO C03296 r...

Отзывы: