H: Control modes

Control source

The control source parameter selects the method used to control
the modulation of the water heater.  This parameter is adjustable
by the installer by accessing parameter 

H2

.  The control methods

are as follows:

1 - Thermostat.  The control modulates the water heater based
on the user set point and the temperature of the tank sensor
when a tank thermostat is used, or the inlet sensor.

2 - BMS (Building Management System).  The control
modulates the water heater based on the 0 - 10 VDC signal
delivered to the appropriate terminals on the connection board.
When BMS is selected additional parameters for BMS operation
may need to be adjusted.  These can only be accessed by the
optional PC software.  See the Armor Water Heater Smart
System PC Program Instructions Manual for additional BMS
parameter information.

3 - Cascade.  The water heater is part of a group of water heaters
sequenced together.  The designated Leader water heater
determines the total output needed from the group based on the
set point and controlling sensor reading.  It assigns portions of
this output to itself (Leader) and the Member water heaters.
When Cascade is selected, each water heater in the group
requires a unique address (see below).  The default control is
Thermostat.

Cascade address

The water heater designated as the Leader needs to be
programmed with address 0.  All the Member water heaters
require addresses from 1 to 7, and the addresses must be
different for each Member.  The addresses can be in any order,
regardless of the order in which the units are wired together.
This parameter is adjustable by the installer by accessing
parameter 

H3

.  The tank sensor must be connected to the Leader

water heater.  The default address is 1.

Max. cascade set point - Not used

Cascade offset - Not used

Cascade off-on differential - Not used

D: Functions

Reset last 10 errors

The reset last 10 errors parameter allows the error counter to be
reset to 0.  This parameter can only be cleared by the installer by
accessing parameter 

D1

.  Once accessed, press the RESET key to

clear the counter.

Service mode delay

By pressing the pin button on the front of the display for five (5)
seconds, the control will be placed in Service Mode.  This will
override all other heat demands.  The Service Mode allows the
installer to set the unit to either maximum firing rate or
minimum firing rate for the purpose of combustion analysis.
The delay sets the length of time the water heater will stay in the
Service Mode if no keys have been pressed before going back to
its original state.  This parameter can only be changed by the
installer by accessing parameter 

D2

.  The time range of this

parameter is 0 to 40 minutes.  The default value is 20 minutes.

E: WHR settings

Tank set point

When a DHW call for heat becomes active, the control will use
the tank set point to determine the firing rate of the water heater
based on the actual water temperature.  This parameter can be
changed by the installer by accessing parameter 

E3

.  The

temperature range of this parameter is 50°F to 190°F.  The
default value is 180°F.

F: Not used

G: Not used

Содержание ARMOR 150

Страница 1: ...n Read all instructions including this manual and the Armor Water Heater Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe p...

Страница 2: ...ntenance that are important but not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing wate...

Страница 3: ...when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines Avoid breathing dust and contact with skin and eyes Use NIOSH certified dust respira...

Страница 4: ...ation Armor water heater operation A General C Data Logging D Functions E WHR Settings H Control Modes I Circulation Pumps J Service Notification Maintenance Service and maintenance schedules Address...

Страница 5: ...1 Service Service Manual 5 The Armor water heater display...

Страница 6: ...ER BUILDING MANAGEMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE SENSOR FLUE GAS SENSOR HIGH LIMIT SENSOR FLAME SENSOR LOW WATER CUTOFF OPTIONAL BLOCKED DRAIN SWI...

Страница 7: ...GE CONNECTION BOARD SMART SYSTEM CONTROL BOARD ALARM BELL AUX DEVICE RELAY RUNTIME CONTACTS SEQUENCER BUILDING MANAGEMENT SYSTEM DHW PUMP IGNITER BLOWER GAS VALVE DISPLAY PANEL PC INTERFACE Control ou...

Страница 8: ...nces of operation for water heating operation Access modes User The user can adjust water heating set point using the UP and DOWN buttons at any time during normal operation By entering the USER code...

Страница 9: ...nce the prepurge cycle is complete and the blocked drain switch is closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve W...

Страница 10: ...to toggle menu listing DOWN If the code is entered incorrectly the display will return to its previous mode You will have to start over at step 1 to enter the code COMMENTS Digit shown underlined at...

Страница 11: ...l flash H3 Cascade Addr H3 will flash H3 Cascade Addr H2 will stop flashing parameter value will appear H3 Cascade Addr UP or DOWN Parameter will increase or decrease depending on button pressed H3 Ca...

Страница 12: ...o No Yes Yes DATA FUNCTIONS E 3 Tank Set Point 14 Yes Yes Yes Yes LOGGING WHR SETTINGS The parameters for Building Management System operation are not listed in this table They are only accessible usi...

Страница 13: ...nternal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for water heating This feature is only used when a tank sensor is used This pa...

Страница 14: ...ddresses must be different for each Member The addresses can be in any order regardless of the order in which the units are wired together This parameter is adjustable by the installer by accessing pa...

Страница 15: ...rol determines that a scheduled service is due based on the hours of actual operation the water heater display will alternate the standard water heater display text with the message SERVICE DUE every...

Страница 16: ...up checkout and performance verification per Section 10 in the Armor Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat ex...

Страница 17: ...these are present in the water heater intake air vicinity they must be removed If they cannot be removed reinstall the air and vent lines per this manual and the Armor Water Heater Installation and O...

Страница 18: ...ter Heater Installation and Operation Manual before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspe...

Страница 19: ...d securely attached Check control settings 1 Set the SMART SYSTEM control module display to Parameter Mode and check all settings See Section 1 of this manual Adjust settings if necessary See Section...

Страница 20: ...ance instructions for the water heater in Section 10 Startup of the Installation and Operation Manual Do not drain the water heater unless it will be exposed to freezing temperatures If using freeze p...

Страница 21: ...mum 4 inches w c natural 8 inches w c LP with gas flowing verify during water heater startup Check control module fuses ALWAYS check control module fuses before replacing control module or any major c...

Страница 22: ...ontrol board Blown fuse Replace fuse F3 on the main control board see page 21 of this manual No Burner Operation Main control board temperature set point satisfied Review temperature setting Remote th...

Страница 23: ...F Resistance Temperature F Resistance 68 14 773 176 1 707 86 9 804 194 1 266 104 6 652 212 952 122 4 607 230 726 140 3 252 248 560 158 2 337 Checking temperature sensors The water heater temperature s...

Страница 24: ...water pressure Verify system pressure is a minimum of 12 PSI No Pump Operation Blown fuse Replace fuse F5 on the control board see page 21 of this manual Faulty pump Replace pump Faulty pump relay Re...

Страница 25: ...ck for loose or misplaced jumpers if flow switch is not installed Blown fuse Replace fuse F2 on the control board see page 21 of this manual Blocked Drain SW will require a manual reset once condition...

Страница 26: ...ted and is not damaged Verify that the vent air intake pipes are correctly installed and that there are no obstructions Check for 24 VAC to the gas valve at the 2 pin connection on the side of the mai...

Страница 27: ...ir inlet is connected and is not damaged Verify that the vent air intake pipes are installed correctly and there are no obstructions Check for 24 VAC to the gas valve at the 2 pin connection on the si...

Страница 28: ...e condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The actual fan RPM is 30 lower than what is being called for Vent air intake lengths exceed the maximum allow...

Страница 29: ...page 23 of this manual Replace the sensor if necessary Sensor Shorted will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset Eit...

Страница 30: ...mor Water Heater Installation and Operation Manual for water heater pump specifications Outlet water temperature has exceeded the maximum outlet water temperature Verify that the system is full of wat...

Страница 31: ...e main control board if necessary If 120 VAC is present on a call for heat and the water heater pump is not operating replace the pump Verify that the water heater pump is set to the proper speed or t...

Страница 32: ...Table 3F Troubleshooting Chart Combustion Levels POSSIBLE CAUSE CORRECTIVE ACTION Vent Air Intake Length or Obstruction Refer to Section 3 General Venting of the Armor Water Heater Installation and O...

Страница 33: ...four 4 adjustments and the combustion is still not within the specified range revisit the possible causes in Table 3F on page 32 or replace the gas valve Figure 3 2 Gas Valve Adjustment Models 150 285...

Страница 34: ...gas valve Figure 3 4 Gas Valve Adjustment Model 500 Service Manual 3 Troubleshooting continued Models 600 800 Locate the throttle adjustment screw on top of the gas valve see FIG 3 4 Using an Allen w...

Страница 35: ...35 NOTES...

Страница 36: ...ns in vent terminations and safety shutoff testing and instructions Revision E ECO C02738 reflects the addition of the Gas Valve Adjustment Procedure for a 399 model on page 33 Revision F ECO C03296 r...

Отзывы: