background image

HP User Manual 

firmware 3.1 

Rev.04 

IT 9/ 51

 

 

Pressing up button 

 you’ll access the the following page. 

 

 

This page is active when regulation probe is the supply air sensor 

 

 

 

his page is active when regulation probe is the return air sensor 

 

 

 

 

 

 
 
 

 

Содержание HPH

Страница 1: ...Electronic Control HPH HPR HPS User Manual HP EN MC00005_04 EN 01 2016 Firmware 3 1 True life inside air and water handling for a confortable life ...

Страница 2: ...HP User Manual firmware 3 1 Rev 04 IT 2 51 ...

Страница 3: ... 19 4 8 G b Information 19 4 9 G c Summer Winter 20 4 10 G d Working hours 20 4 11 G e BMS config 21 4 12 G f Service setting 21 4 12 1 G f a Working hours set 21 4 12 2 G f b Probe adjustment 22 4 12 3 G f c Thermoregulation 24 4 12 4 G f d User DEV Change PW1 28 4 13 G g Manual management 28 4 14 H Manufacturer 29 4 15 H a Configuration 29 4 16 H b I O Configuration 31 4 17 H c Factory settings ...

Страница 4: ... recovery management Water coil anti freeze management ON OFF electric heater management Filter pressure switch management Management of ventilation with CO2 probe Management of ventilation with one or two pressure sensors Free cooling modulating management Free heating modulating management Management of mixing chamber Management of motorized dampers Alarms management Post ventilation Weekly prog...

Страница 5: ...tons Set Display address setting to 31 and press When the display is ON press together the indicated buttons Press twice Set as shown the following screen Then select Ok set Yes and press Now the matster board is configured Display address Setting 21 I O Board address 01 Terminal config Press ENTER to continue P 01 Adr Priv Shared Trm1 32 Sh Trm2 21 Sh Trm3 None Ok No max 50 m Local terminal Remot...

Страница 6: ...UTTON PRG Enter in main menu root BUTTON ESC Back BUTTON UP Scroll up or value increase On main screen direct access to set point menu BUTTON DOWN Scroll down or value decrease BUTTON ENTER Enter in the selected submenu or confirm setting BUTTON ESC BUTTON UP On main screen turn ON OFF the unit BUTTON ESC BUTTON DOWN Switch visualisation parameters circuit 1 or 2 Display contrast setting Press sim...

Страница 7: ...rmation sto see the unit working mode On this windows you can see the working mode STATE UNIT Unit off by Alarm Unit off by Supervision Unit off by Scheduler Unit off by Digital input Unit off by keyboard State mode unit Manual Cold Manual Hot Auto Cold Auto Hot Defrost State Heat recovery Defrost Heat pump defrost Clock State Unit Date ...

Страница 8: ...HP User Manual firmware 3 1 Rev 04 IT 8 51 Pressing down button you ll access the the following page Electric Pre Heater State Electric Post Heater State Compressor State ...

Страница 9: ...firmware 3 1 Rev 04 IT 9 51 Pressing up button you ll access the the following page This page is active when regulation probe is the supply air sensor his page is active when regulation probe is the return air sensor ...

Страница 10: ...er Winter d Working hours e BMS config f Service settings a Working hour set b Probe adjustment c Thermoregulation d User DEV Change PW1 g Manual management H Manufacturer a Configuration Compressor Inverter a Configuration b Regolation c Custom Driver EVD EVO o EVO OnBoard a Configuration b Regolation c Custom b I O Configuration c Factory settings d Initialization e Input Output Test To access t...

Страница 11: ...STO ESC TASTO SU Premere contemporaneamente i tasti Esc UP per accendere spegnere l unità 4 2 B Setpoint The following figures shows the set point screens Page active with regulation on return air sensor automatic mode Page active with regulation on return air sensor manual mode Page active with dehumidification active Page active with air quality sensor active active ...

Страница 12: ...mmer time enabling and setting Scheduler enabling Profile 1 Profile 2 Profile 3 Profile enabling See the following screens Time and date setting Summer time enabling and setting Scheduler must be enable on the following screen Scheduler enabling You can set on this screen 3 different set points called profiles Each profile includes the automatic and manual unit set points and enabling of night fan...

Страница 13: ...e day schedule on an other day None rectangle Status OFF Low rectangle Profile 1 Medium rectangle Profile 2 High rectagle Profile 3 4 4 D Input Output On this menu you can see the analog and digital input and output status In case of not used I O you ll see ID00 Number of digital input and description B00 Number of analog input and description ...

Страница 14: ...HP User Manual firmware 3 1 Rev 04 IT 14 51 Compressor data screen Heat pump data screen Heat pump data screen NO00 Number of digital output and description ...

Страница 15: ...HP User Manual firmware 3 1 Rev 04 IT 15 51 Compressor data screen EEV data screen Compressor data screen Compressor data screen Compressor data screen Compressor data screen ...

Страница 16: ...HP User Manual firmware 3 1 Rev 04 IT 16 51 Compressor data screen Compressor data screen ...

Страница 17: ...HP User Manual firmware 3 1 Rev 04 IT 17 51 ...

Страница 18: ...story to reset them you need to enter on service menu password is needed Pressing the alarm button you can mute the buzzer and see the active alarms and reset them of course the alarm log will not be reset and then directly enter in the alarm history menu alarm date alarm clock alarm sequence number ...

Страница 19: ...ivided inn sub menu the first four a b c d are not password protected and allos you to set the following 4 7 G a Change Language Language set up To exit press button 4 8 G b Information you can find information about software code and version and installed electronic board ...

Страница 20: ...HP User Manual firmware 3 1 Rev 04 IT 20 51 4 9 G c Summer Winter Automatic or manual season changeover 4 10 G d Working hours You can see the working hours of the main components installed on the unit ...

Страница 21: ... 11 G e BMS config BMS setting all the parameters necessary to set a BMS communication 4 12 G f Service setting 4 12 1 G f a Working hours set Working hour setting it allows to set the maximum working hour of unit main components that need a periodic maintenance On the same screen you can reset the worked hours of each component ...

Страница 22: ... firmware 3 1 Rev 04 IT 22 51 4 12 2 G f b Probe adjustment Sensors calibration you can set an offset to add or remove on each sensor reading Once confirmed the sensor value is automatically updated reported on side ...

Страница 23: ...HP User Manual firmware 3 1 Rev 04 IT 23 51 ...

Страница 24: ...HP User Manual firmware 3 1 Rev 04 IT 24 51 4 12 3 G f c Thermoregulation Setting of thermoregulation Screen active with free cooling active ...

Страница 25: ...HP User Manual firmware 3 1 Rev 04 IT 25 51 Screen active with free cooling active Screen active with free heating active Screen active with free heating active ...

Страница 26: ...HP User Manual firmware 3 1 Rev 04 IT 26 51 R1 R2 R3 QPM2100 QPM2100 remove jumper QPM2100 remove jumper R3 R3 jumper open 0 5V R3 jumper close 0 10V ...

Страница 27: ...HP User Manual firmware 3 1 Rev 04 IT 27 51 Set costant flow pressur sensor Taglia 014 020 026 k 60 95 121 Taglia 050 092 144 205 k 121 197 308 394 ...

Страница 28: ...HP User Manual firmware 3 1 Rev 04 IT 28 51 4 12 4 G f d User DEV Change PW1 User DEV Change PW1 you can reset the alarm history and change the password PW1 4 13 G g Manual management ...

Страница 29: ... main features of the unit and the operation of each component On the following screens you can see the features of the installed components and the hardware seting You can also see the EEV driver setting a Configuration b Regolation c Custom and of the compressor driver a Configuration b Regolation c Custom These parameters are related to the serial port of the compressor driver ...

Страница 30: ...HP User Manual firmware 3 1 Rev 04 IT 30 51 These parameters are related to the serial port of the compressor driver ...

Страница 31: ...HP User Manual firmware 3 1 Rev 04 IT 31 51 4 16 H b I O Configuration I O Configuration On this menu you can activate and set each I O ...

Страница 32: ...HP User Manual firmware 3 1 Rev 04 IT 32 51 ...

Страница 33: ...HP User Manual firmware 3 1 Rev 04 IT 33 51 4 17 H c Factory settings Factory setting the following screens allows the set all the manufacturer reserved parameter ...

Страница 34: ...HP User Manual firmware 3 1 Rev 04 IT 34 51 ...

Страница 35: ...HP User Manual firmware 3 1 Rev 04 IT 35 51 ...

Страница 36: ...HP User Manual firmware 3 1 Rev 04 IT 36 51 ...

Страница 37: ...P User Manual firmware 3 1 Rev 04 IT 37 51 4 18 H d Initialization Default installation complete reset of the default value On this screen you can change the manufacture value 4 19 H e Input Output Test ...

Страница 38: ...nnection diagram between BMS and uPC MASTER GND RX TX RX TX Fig 8 a Note Suggested cable for data line with 100 120ohm impedance type BELDEN 3105A EIA Industrial RS 485 PLTC CM The following table shows the variables shared with supervisor Nota On the first column shows the Carel address the second one the ModBus address packet in case of register communication mode the address of the ModBus colum...

Страница 39: ...11 DIGITAL INPUT 10 Din10_msk Status of digital input 0 Closed 1 Open 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 DIGITAL OUTPUT 1 Dout1_Value 0 Open 1 Close 21 22 DIGITAL OUTPUT 2 Dout2_Value 0 Open 1 Close 22 23 DIGITAL OUTPUT 3 Dout3_Value 0 Open 1 Close 23 24 DIGITAL OUTPUT 4 Dout4_Value 0 Open 1 Close 24 25 DIGITAL OUTPUT 5 Dout5_Value 0 Open 1 Close 25 26 DIGITAL OUTPUT 6 Dou...

Страница 40: ...nsing temperature 122 123 A022 Low suction temperature 123 124 A023 Autotune Valve A 124 125 A024 Autotune Valve B 125 126 NOT USED NOT USED 126 127 NOT USED NOT USED 127 128 A027 High Pressure Alarm Compressor 1 128 129 A028 Low Pressure Allarm Compressor 1 129 130 A029 Disabled Compressor Start DP 130 131 A030 Air Flow Switch ID 131 132 A031 Fan Alarm ID 132 133 A032 Filter Pressure Switch Suppl...

Страница 41: ...sor 1 suction temp 5 6 ANALOG INPUT VALUE 5 Ain5_Std_UM Compressor 1 discharge temp 6 7 ANALOG INPUT VALUE 6 Ain6_Std_UM C1 high pressure transducer 7 8 ANALOG INPUT VALUE 7 Ain7_Std_UM C1 low pressure transducer 8 9 ANALOG INPUT VALUE 8 Ain8_Std_UM Saturation temp 9 10 ANALOG INPUT VALUE 9 Ain9_Std_UM Return air temp 10 11 ANALOG INPUT VALUE 10 Ain10_Std_UM Return air humidity 11 12 ANALOG INPUT ...

Страница 42: ... uency_Rps Minimum drive output frequency rps 205 206 Motor_Current Motor current 1 10 A 206 207 Inverter_Req_0_1000 Speed request to inverter filtered by envelop 0 1000 1 10 207 208 A100_DISCHARGE_SH_ SET_1 SetPoint of Discharge SH EE Valve subregulation 1 10 C 208 209 A101_DISCHARGE_TEM P_SET_1 SetPoint of Discharge Temp EE Valve subregulation 1 10 C 209 210 MOP_Inhibition_Thr_1 to EVD Pin of MO...

Страница 43: ...perature valve A 313 314 314 315 A17_EEV_POSITION_PE RCENT_SHOW 315 316 316 317 A7_SH_EVAP_PRES Evaporation pressure valve A 317 318 A6_SH_EVAP_TEMP Evaporation temperature valve A 318 319 319 320 320 321 321 322 322 323 323 324 324 325 325 326 326 327 327 328 328 329 CAREL MODBUS INTEGER 3 INTEGER MODBUS TAG NAME TAG DESCRIPTION 1 5003 Unit_Status Unit ON OFFbyALR OFFbyNET OFFbyBMS OFFbyFSC OF Fb...

Страница 44: ...de 0 No fault 1 Overcurrent 2 Motor overload 3 Overvoltage 4 Undervoltage 5 Drive overT 6 Drive underT 7 Overcurrent HW 8 Motor overtemp 9 Reserved 10 Cpu error 11 Param default 12 DC bus ripple 13 Data comms fault 14 Drive thermistor 15 Autotune fault 16 Drive disabled 17 Motor phase 18 Fan fault 19 Speed fault 110 5112 111 5113 112 5114 113 5115 114 5116 115 5117 116 5118 117 5119 118 5120 119 5...

Страница 45: ...211 Circuit_Cooling_Capacity_Env_A Actual circuit cooling capacity for EVD valve from envelope 210 5212 I89_REGULATION_SUB_TYPE_1 regulationsubtipe 211 5213 Env_Countdown_1 Countdown of out of envelop alarm s 212 5214 Envelope_Zone_1 Envelopeworking zone 0 Null 1 OK 2 Max comp R 3 Max disch P 4 HCurr 5 Max suct P 6 Min comp R 7 LowDP 8 Min disch P 9 Min suct P 213 5215 Disch_Temp_Zone_1 Discharge ...

Страница 46: ...HP User Manual firmware 3 1 Rev 04 IT 46 51 308 5310 309 5311 310 5312 ...

Страница 47: ...043R0 0 17 3bar A011 S2 sensor failure Compressor Suction Temp Check wiring and sensor type NTC030WF00 A012 S3 sensor failure High pressure Check wiring and sensor type SPKT00B6R0 0 44 8bar A013 S4 sensor failure Compressor discharge Temp Check wiring and sensor type NTC030HTF00 A014 LowSH Low overheating valve A Contact service dept A015 LowSH Low overheating valve B NOT USED A016 LOP Low evapora...

Страница 48: ...o switch Alarm Check digital input DI5 A041 High Pressure Prevention Function Reduced operation mode warning 1 Summer mode bassa exhaust airflow too low a exhaust airflow too low b dirty filters or clogged ductwork c air conditions over limit 2 Winter mode supply airflow too low a supply fan speed too low b dirty filters or clogged ductwork c air conditions over limit 4 Freon filling too high A042...

Страница 49: ...h voltage 4 Low voltage 5 High temperature 6 Low temperature 7 HW overcurrent 8 Motor High temperature 9 Drive fault 10 Cpu error 11 Default parameters 12 DC bus ondulation 13 timeout com ser 14 Thermistor error 15 Autotuning error 16 Drive disabled 17 Motor missing phase 18 Fan fault 19 Motor stalemate 20 PFC module fault 21 Alarm code 21 22 PFC low voltage 23 STO reading error 24 STO reading err...

Страница 50: ...m h V Min HPS 360 630 780 1440 2310 3420 3960 HPS Set DP Pa MAX HPR H 400 489 574 2219 2325 1921 2325 DP Pa V k Set DP Pa MAX HPS 400 489 462 1574 1528 1370 1122 Set DP Pa Min HPR H 36 44 52 200 209 173 209 DP Pa V k Set DP Pa Min HPS 36 44 42 142 137 123 101 FSS Pressure sensor range Pa 1000 1000 1000 5000 5000 5000 5000 Signal 0 10V MAX HPR H 40 49 57 44 47 38 47 Set FSS 100 Signal 0 10V MAX HPS...

Страница 51: ..._______ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ __________________________________________________________ ______________________________________...

Отзывы: