Successful
Successful
Successful
Successful start
start
start
start condition
condition
condition
condition setup
setup
setup
setup considerations:
considerations:
considerations:
considerations:
1:Starter and the engine, there are four separate conditions, the magnetic sensor, gens frequency, oil
pressure, charge D, both may be used alone. Recommended oil pressure must comply with magnetic
sensors, gens simultaneously, purpose is to make the starting motor and engine as soon as possible
separation and accurate judgment starting successfully.
2:Magnetic sensor is a magnetic device is installed in the engine block detection flywheel tooth number.
3:When choosing the magnetoelectric sensor, ensures that the engine flywheel tooth number and the set
value, otherwise it may appear overspeed shutdown or less speed down.
4:If the generator without magnetoelectric sensor, please do not select the corresponding item, or there
will be a starting unsuccessful or speed loss of signal alarm shutdown.
5:If the generating units without oil pressure sensor, please do not select the corresponding item.
6:If successful starting conditions did not choose the generator, related to power the controller does not
capture and display power ( which can be applied to the pump unit ), if the start condition did not choose
the magnetic sensor, the controller display speed by power signal conversion.
7:If the generator without magnetoelectric sensor and Oil pressure sensor,the “ Charger D+” is optional
as a starter motor separation conditions. It is recommended to select “Oil Pr Charger D+” for
safety.
8.
8.
8.
8.COMMISSIONING
COMMISSIONING
COMMISSIONING
COMMISSIONING
Please make the under procedures checking before commissioning,
1.
Ensure all the connections are correct and wires diameter is suitable.
2.
Ensure that the controller DC power has fuse, controller’s positive and negative connected to start
battery are correct.
3.
Emergence stop must be connected with positive of start battery via scram button’s normal close
point and fuse.
4.
Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire of fuel
value). If checking is OK, make the start battery power on; choose manual mode and controller will
executive routine.
5.
Set controller under manual mode, press “start” button, genset will start. After the setting times as
setting, controller will send signal of Start Fail; then press “stop” to make controller as reset.
6.
Recover the action of stop engine start (e. g. Connect wire of fuel value), press start button again,
genset will start. If everything goes well, genset will normal run after idle running (if idle run be set).
During this time, please watch for engine’s running situations and AC generator’s voltage and
frequency. If abnormal, stop genset running and check all wires connection according to this manual.
7.
Select the AUTO mode from controller’s panel, connect mains signal. After the mains normal delay,
controller will transfer ATS (if fitted) and into mains load. After cooling time, controller will stop genset
and make it in to “at rest” mode until there is abnormal of mains.
8.
When mains is abnormal again, genset will be started automatically and into normal running, then
controller send signal to make generator switch on, and control the ATS as generator load. If not like
this, please check ATS’ wires connection of control part according to this manual.
9.
If there is any other question, please contact Feirui’s service.