LXC63X0/LXC51X0
Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC63X0/LXC51X0
Generator controller user manual.
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
23 of 36
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
23 of 36
65
Output 6 way
(0-1)
1
0:Normally open output,
1:Normally closed output
66
Input function selection 1
(1-29)
13
13:Remote start load
67
Input 1 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
68
Input Trigger Event 1
(0-3)
Controller Fixed setting
69
Valid input 1
(0-3)
70
Input function selection 2
(1-29)
19
19:High temperature warning input
71
Input 2 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
72
Input Trigger Event 2
(0-3)
Controller Fixed setting
73
Valid input 2
(0-3)
74
Input function selection 3
(1-29)
20
20:Low oil pressure warning input
75
Input 3 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
76
Input Trigger Event 3
(0-3)
Controller Fixed setting
77
Valid input 3
(0-3)
78
Input function selection 4
(1-29)
9
9:Low oil pressure stop
79
Input 4 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
80
Input Trigger Event 4
(0-3)
Controller Fixed setting
81
Valid input 4
(0-3)
82
Input function selection 5
(1-29)
6
6:Highe water temperature alarm
83
Input 5 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
84
Input Trigger Event 5
(0-3)
Controller Fixed setting
85
Valid input 5
(0-3)
86
Input function selection 6
(1-29)
24
24:External alarm input
87
Input 6 activation
(0-1)
0
0:Closed Activation,
1:Disconnect Activation
88
Input Trigger Event 6
(0-3)
Controller Fixed setting
89
Valid input 6
(0-3)
90
Power-up mode
(0-2)
0
0:Stop Mode,
1:Manual Mode,
2:Automatic mode
91
Module address
(1-254)
1
Controller mailing address.
92
Password Settings
(0-9999)
0000
93
Starting conditions for
success
(0-7)
2
Engine starter separation conditions:
generation, magnetic sensors, oil;
purpose: to make the starter motor and
the engine quickly separated. * Table 7.8
94
Successful start speed
(0-3000RP
M)
450
When the engine speed exceeds this
value, the unit, starter will disconnect.
95
Successful start
frequency
(10-30HZ)
15
When the engine frequency exceeds this
value, the unit, starter will disconnect.
96
oil successful start
(0-400kPa)
200
When the engine oil exceeds this value,
the unit, starter will disconnect.
97
Successful start D+
(
3-32V
)
8
Successful start, the D+ terminal voltage.