LXC63X0/LXC51X0
Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC63X0/LXC51X0
Generator controller user manual.
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
27 of 36
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
27 of 36
79
Automatic stop
prohibited
In the automatic mode, the generator during normal operation, when
the automatic shutdown disable input effective action.
80
Idle/ run control
This output is active from cranking, continues to be active until the
start idle timer has elapsed; Also this output is active during the
period of the stop idle timer, continues to be active until the engine
has stopped.
81
The oil output
In the starting - Safety during operation action.
82
Raise speed
This output is active during the warming up timer.
83
Excite generator
This output is available for the period of the crank timer. This output
will energize for 2 second during the period of the safety on timer if
generator has no voltage.
84
Drop speed
This output is available during the period of the coolant down timer,
and remain until the engine has stopped.
85
Oil pressure output
Action during the safe operation of preheating.
86
High temperature 2
warning
Action when high temperature 2 warning alarm.
87
High temperature 2
shutdown
Action when high temperature 2 shutdown alarm.
88
Low oil pressure 2
warning
Action when low oil pressure2 warning.
89
Low oil pressure 2
shutdown
Action when low oil pressure2. shutdown.