LXC63X0/LXC51X0
Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC63X0/LXC51X0
Generator controller user manual.
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
20 of 36
�
:
T:+86 0769-23162896
�
:
F:+86 0769-23166296
�
::::
www.lixise.com
Page
20 of 36
7.3.
7.3.
7.3.
7.3. Parameter
Parameter
Parameter
Parameter setting,
setting,
setting,
setting, content
content
content
content and
and
and
and scope
scope
scope
scope of
of
of
of list
list
list
list
No
No
No
No
Menu
Menu
Menu
Menu
Range
Range
Range
Range
Defa
Defa
Defa
Defa
ult
ult
ult
ult
Description
Description
Description
Description
1
Mains transient
(0-30s)
2
When the mains voltage from abnormal to
normal or abnormal from normal to
confirm the time for switching the ATS.
2
Mains Under Voltage
(50-360/
624)V
184
When the sampling voltage is below this
value, namely that the mains voltage is
too low, when set to 30V,low voltage
signal is not detected, hysteresis is 10V.
3
Mains Over voltage
(50-360/
624)V
176
When the sampling voltage is higher this
value, namely that the mains voltage is
too high, when set to 620V, high voltage
signal is not detected, hysteresis is 10V.
4
Mains Under Frequency
(0-75Hz)
45
5
Mains Over Frequency
(0-75Hz)
55
6
Switching Transfer time
(0-100s)
2
From the mains is opened to the gens is
close or from the gens is opened to mains
close interval times.
7
Start delay
(0-9999s)
1
Time from mains abnormal or remote start
signal is active to start genset.
8
Stop Delay
(0-9999s)
1
Time from mains normal or remote start
signal is inactive to gen-set stop.
9
Number of starts
(1-10)
3
Fail to start the engine, the maximum number
of starts. When you reach the set number of
starts, the controller sends start fail signal.
10
Preheat Delay
(0-300s)
0
Time of pre-powering heat plug before
starter is powered up.
11
(3-60s)
8
Time of starter power up.
12
Crank Rest Time
(3-60s)
10
The waiting time before second power
up when engine start fail.
13
Safety On Delay
(1-60s)
10
Alarms for low oil pressure high temp,
under speed, under frequency /voltage,
charge fail are inactive.
14
Start Idle Time
(0-3600s)
0
Idle running time of genset when starting.
15
(0-3600s)
10
Warming time before genset switch on,
after it into high speed running.
16
Cooling time
(0-3600s)
10
Radiating time before genset stop, after it
unloads.
17
Stop idle time
(0-3600s)
0
Idle running time when genset stop.
18
ETS Solenoid Hold
(0-120s)
20
Stop electromagnet's power on time when
genset is stopping.
19
Fail To Stop Delay
(10-120s)
0
When the "ETS output time" is set to 0,
the delay from the end of idle time
required to complete stop; when "ETS
output time" is not equal to 0, the ETS
delay from the end to complete stop
required of the time.
20
Closing pulse time
(0-5s)
5
Mains closing and gen closing pulse width
of 0 means continuous output.