3.2.3  Zone Touchpads 

The zone touchpads house the zone sensors and must be mounted  

 

 

 

within the area controlled by the corresponding motorised damper.  
The ideal position is 1.5 m off the floor in the return air path. Care  

 

must be taken to avoid solar radiation, wall cavity drafts and other  

 

heat sources. 

The LCD zone touchpads allow the user to adjust various aspects of the indoor climate. By 
default access to all control functions is available from all LCD touchpads.

Access to some control functions from individual touchpads may be limited via hardware DIP switch 
settings during installation. These DIP switches are located on the back of each LCD zone 
touchpad. 

If access to a function has been limited the LCD touchpad will respond with a beep only. 

Connect LCD Touchpad DIP switch functions

Function

Description

DIP switch position

1

2

3

4

Factory 

Default

The factory default allows full access to 

all controller functions. No screen change 

when backlighting goes off.  

OFF

OFF

OFF

OFF

My Zone  

Lock

Access setpoint and clock functions for this 

zone only. No access to other zones.

ON

OFF

OFF

OFF

My Zone 

Return

Full access. Display defaults to this zone 

when backlighting goes off.

OFF

ON

OFF

OFF

Setpoint  

Limit

Full access with setpoint range limited to  

20 - 25 °C for this zone touchpad.

OFF

OFF

ON

OFF

Mode  

Lock

Full access excluding mode changes which 

are disabled from this zone touchpad.

OFF

OFF

OFF

ON

Summary 

Return

Full access. Display returns to summary 

screen when backlighting goes off.

ON

ON

OFF

OFF

3.2.4  Motorised Dampers 

The motorised barrel dampers must all have the same motor type,  

 

 

and should be fitted in line in the flexible duct. 

3.3  Control Wiring 

 

•  All control wiring to touchpads and motors is by RJ12 type connectors, with the exception 

of the 24 VAC supply to the Livezi Connect main modules.  
Refer to Appendix B for control cable crimping instructions. 

•  Shielded cable is recommended for all data connections to minimise the possibility of 

external interference. 

•  Data cables are to be kept the maximum practical distance from any LV power supply 

cables ≥ 240 volts (Minimum distance 300 mm). 

•  Maximum cable length is not to exceed 50 m.  

Suggested cabling: Livezi supplies and recommends the following cable:  
RM-CAB-6-100 - six core flat cable for damper motors  
RM-CAB-S-100 - five core + shield flat cable for all data connections and touchpads. 

Содержание C-CCT-1210

Страница 1: ...ration ready We talk to anyone iPad Interface SET MODE ZONE CLOCK Activ e 5 Cooli ng SET MODE ZONE CLOCK Active 5 Cooling SET MODE ZONE CLOCK Activ e 5 Cooli ng SET MODE ZONE CLOCK Activ e 5 Cooli ng...

Страница 2: ...to make changes and improvements to any of the products described in this docu ment without prior notice Under no circumstances shall Livezi be responsible for any loss of income or any special incide...

Страница 3: ...Zones 9 4 2 Initial Power On 9 4 3 Set Airflow Profiles 9 4 4 System Configuration 10 5 4 1 Set Cooling Performance 10 5 4 2 Set Heating Performance 10 5 4 3 Set Motor Type 10 5 4 1 Set Minimum Venti...

Страница 4: ...g a Zone Temperature 19 7 6 Naming Zones 19 7 7 Setting the Clock 20 7 8 Setting the System Timer Program 20 7 9 Setting Individual Zone Timer Programs 21 Appendix C Airflow Management 22 D 1 Airflow...

Страница 5: ...hat all electrical connections are secure or warranty will be void Field or installation wiring must be connected as per the connection diagram to ensure the unit performs as it is designed Refer to A...

Страница 6: ...l run on any iOS device iPad Ipod Iphone It takes advantage of the large canvas associated with the iPad to provide an intuitive user interface 3 2 1 Chatterbox HVAC Livezi chatterbox creates a page f...

Страница 7: ...ve 5 Cool ing 4 5 2 3 1 Figure 3 2 3 2 1 Connect Main Processor Module The main processor module is best installed on or near the indoor unit Maintain a minimum distance of 300 mm from sources of EMI...

Страница 8: ...er zones ON OFF OFF OFF My Zone Return Full access Display defaults to this zone when backlighting goes off OFF ON OFF OFF Setpoint Limit Full access with setpoint range limited to 20 25 C for this zo...

Страница 9: ...tailored to suit the individual requirement of the space it controls Zone Profiling includes a maximum open position on the damper and an airflow range 4 3 1 Set Zone Maximum Open Profile Each zone i...

Страница 10: ...e top line 2 Use or to alter the heating delay setting then press SET to save and proceed to the next step 4 4 3 Set Motor Type The Livezi Connect utilises a time proportional damper positioning algor...

Страница 11: ...er the timer setting then press SET to save and exit system configuration 4 5 Final Zone Check 1 Select the global screen and press to turn all zones ON 2 Press or to select the first zone 3 Turn the...

Страница 12: ...fitted and sealed Condensate lines do not rise above the floor level of the unit Condensate lines are properly trapped Ductwork is securely fixed to the unit The unit is slung or mounted on suitable...

Страница 13: ...Access to some control functions may be limited via hardware settings during installation Refer to section 3 2 3 Zone Touchpads In the following pages functions which may be limited in this manner wil...

Страница 14: ...e selection screen 2 Use or to alter the mode 3 Press SET to save and exit 6 4 Selecting the Zone mode The mode of operation for individual zones can be selected from each zone screen of the LCD touch...

Страница 15: ...st the return air target temperature 3 Use or to adjust the set point to the desired level 4 Press SET to save and exit 6 8 Naming a zone Zone names must be eight characters in length A blank characte...

Страница 16: ...ram then press SET 4 Use or to highlight desired program A or B then press SET 5 The top line will scroll Program ALL Zones ram Days sMTWTFs 6 On the bottom line the days of the week are displayed A C...

Страница 17: ...xit at this point If there are valid days the top line will scroll Program start Zone x s tart Z 0 8 4 0 a m 5 Use or to alter the start time to the correct value in 10 minute intervals 6 Press SET to...

Страница 18: ...selection Functions as back button in menu system Select menu options Save variables and advance to next field Turn system or zone on and off LED below is illuminated when system is on Active 7 Mode...

Страница 19: ...equired Tips To accept one of the preset zone names press SET repeatedly to accept each character including any blanks until the controller reverts to the standard display When adding a custom name it...

Страница 20: ...hen press SET 4 Use or to highlight desired program A or B then press SET 5 The top line will scroll Program ALL Zones ram Days sMTWTFs 6 On the bottom line the days of the week are displayed A CAPITA...

Страница 21: ...next day Repeat for each day 4 Press SET after the final day value to enter the Start time screen Note If no days have been selected the configuration routine will exit at this point 5 Use or to alter...

Страница 22: ...t is fully closed and the damper to the other is fully open In this instance the VAV system status is the same regardless of which VAV damper is open Actual system open 50 Example 2 Now consider the c...

Страница 23: ...system In the examples on the previous page the following settings will have the desired effect Example 1 Both zones Airflow profile 200 Nominal system airflow requirement 200 Example 2 Large zone Ai...

Страница 24: ...utdoor coil sensor short circuit Indoor coil sensor open circuit Indoor coil sensor short circuit Fault D3 High Pressure or Low pressure Fault Line 2 scrolls one of the following HP compressor safety...

Страница 25: ...r open circuit Outdoor coil sensor short circuit Indoor coil sensor open circuit Indoor coil sensor short circuit Fault I3 Contact Manufacturer Line 2 scrolls one of the following Contact Manufacturer...

Страница 26: ...34 0 c Outoor coil sensor CompLoad Line1 In 36 0 c Indoor coil sensor Line2 LD 100 Compressor load Defrost Line1 Defrost Line2 Ok or DeIce or DeWater 3 Phase Line1 scrolls L1 Ok L2 Down L3 Down state...

Страница 27: ...To Indoor Unit...

Страница 28: ...Livezi Phone 1300 306 125 Fax 07 3890 8734 Web www livezi com au Email info livezi com au Registration www livezisupport com...

Отзывы: