iGrow 1800 Installation Guide
Page61
Link4 (714) 524-0004
iGrow-to-iGrow Link
Zone Master
Zone 2
Channels 01 to 12
Use Local Setpoint
Note:
Be sure that ZoneMaster Units are set up in sequential order. For Example, if you have three Zone
Masters, set their zone numberto be in order i.e. 2,3,4. DO NOT jump over one such as 2,4,5. The
iControl software will not function properly.
Slave Unit
For Slave Units (also called Expansion Units), set to
Slave Unit
. Then set which zone the unit will be an
expansion unit to, i.e. Site Master Zone 1, or some other Zone Master. Since each zone can have up to 3
Expansion Units you must also decide which expansion unit it is.
•
Expansion Unit Outputs 13-24
•
Expansion Unit Outputs 25-36
•
Expansion Unit Outputs 37-48
Note:
Be sure that Expansion Units are set up in sequential order. For Example, if you have only two
expansion units be sure to set one as 13-24 an the other to 25-36. DO NOT jump over one such as 13-
24 and 37-48. The iControl software will not function properly.
iGrow-to-iGrow Link
Slave Unit
Zone 1
Channels 13 to 24
Use Remote Setpoint
Similar to a Zone Master, you can choose to use
Local
or
Remote
Setpoints. But in this case, if you choose
Remote
setpoints, the Expansion unit will use the Zone Master’s setpoints NOT the Site Master’s setpoints.
Now press the
BACK
button three times (or until you see the Main Status screen) to save your changes.
Note:
Once you setup the Site Master, Zone Master(s) and Expansion Unit(s), you should label the front panel
on each unit for easier reference in the future.
Fallback Settings
Fallback
Sensor Enabled
High Alarm Disabled
Force to NORM
Sensor