Input Connection 

 WARNING 

ELECTRIC SHOCK can kill 
Only a qualified electrician should connect the input 
leads to the Power Wave.  Connections should be made 
in accordance with all local and national electrical codes 
and the connection diagrams located on the inside of the 
reconnect/input access door of the machine.  Failure to 
do so may result in bodily injury or death. 
 
Use a three-phrase supply line. A 45mm diameter 
access hole for the input supply is located on the case 
back. Connect L1, L2, L3 and ground according to the 
Input Supply Connection Diagram. 
 

Input Fuse and Supply Wire 
Considerations 

Refer to Specifications page for recommended fuse and 
wire sizes. Fuse the input circuit with the recommended 
super lag fuse or delay type breakers (also called 
"inverse time" or "thermal/magnetic" circuit breakers). 
Choose input and grounding wire size according to local 
or national electrical codes. Using fuses or circuit 
breakers smaller than recommended may result in 
"nuisance" shut-offs from welder inrush currents, even if 
the machine is not being used at high currents. 
 

Input Voltage Selection 

Welders are shipped connected for the highest input 
voltage listed on the rating plate. To move this 
connection to a different input voltage, see the diagram 
located on the inside of the input access door, or the 
Input Supply Connection Diagram below. If the Auxiliary 
lead (indicated as ‘A’) is placed in the wrong position, 
there are two possible results. 
 
a)  If the lead is placed in a position higher than the 

applied line voltage, the welder may not come on at 
all.  

b)  If the Auxiliary lead is placed in a position lower than 

the applied line voltage, the welder will not come on, 
and the two circuit breakers in the reconnect area 
will open. If this occurs, turn off the input voltage, 
properly connect the auxiliary lead, reset the 
breakers, and try again. 

 

Input Supply Connection for K2803-1 

 WARNING 

ELECTRIC SHOCK CAN KILL: 

 

Do not operate with covers removed 

 

Disconnect input power before servicing 

 

Do not touch electrically live parts 

 

Only qualified persons should install, use or service 
this equipment 

 

 

 
Voltage=380-415V 

 

 
Voltage=440-460V 

 

 
Voltage=500V 

 

 
Voltage=550-575V 

Содержание K2803

Страница 1: ...IM2064 04 2017 REV01 POWER WAVE AC DC 1000 SD CE OPERATOR S MANUAL ENGLISH THE LINCOLN ELECTRIC COMPANY 22801 St Clair Ave Cleveland Ohio 44117 1199 USA www lincolnelectric eu...

Страница 2: ...Head K2312 MAXsa 29 Feed Head Sales codes may contain suffixes and prefixes Is in conformity with Council Directives and amendments Electromagnetic Compatibility EMC Directive 2014 30 EU Low Voltage D...

Страница 3: ...dealer For future reference record in the table below your equipment identification information Model Name Code Serial Number can be found on the machine rating plate Model Name Code Serial number Da...

Страница 4: ...575 3 25 3 25 4 25 4 25 6 16 8 10 8 10 8 10 8 10 10 6 100 90 90 80 70 PHYSICAL DIMENSIONS HEIGHT mm WIDTH mm DEPTH mm WEIGHT kg 1248 501 1184 363 TEMPERATURE RANGES OPERATING TEMPERATURE RANGE C STOR...

Страница 5: ...surement Personal medical devices like pacemakers and hearing aids Check the electromagnetic immunity for equipment operating in or near the work area The operator must be sure that all equipment in t...

Страница 6: ...he work clamp to avoid the risk of accidental arc ignition ELECTRIC AND MAGNETIC FIELDS MAY BE DANGEROUS Electric current flowing through any conductor creates electric and magnetic fields EMF EMF fie...

Страница 7: ...SD CE is primarily designed to interface with compatible ArcLink equipment However it can also communicate with other industrial machines and monitoring equipment via DeviceNet or Ethernet The result...

Страница 8: ...ower Wave AC DC 1000 SD CE demands that enough clearance behind the machine be maintained This is especially important where more than one machine is to be used or if the machines are going to be rack...

Страница 9: ...uisance shut offs from welder inrush currents even if the machine is not being used at high currents Input Voltage Selection Welders are shipped connected for the highest input voltage listed on the r...

Страница 10: ...cts of welding related issues such as Arc Blow The arc to arc phase relationship is determined by the timing of each arc s sync signal relative to the sync signal of ARC 1 DIP Switches on the Control...

Страница 11: ...English English 8 Cruiser Connection Diagram...

Страница 12: ...ve AC DC 1000 SD CE per recommended guidelines Connect Install welding cables per recommended Output Cable Guidelines see Table1 Output Cable Guidelines Open the Power Wave AC DC 1000 SD CE front pane...

Страница 13: ...English English 10 Single Arc Connection Diagram...

Страница 14: ...trode Sense Lead 67 at the feeder and the Work Sense Lead 21 from the Power Wave AC DC 1000 SD CE per recommended guidelines Connect Install welding cables per recommended Output Cable Guidelines see...

Страница 15: ...English English 12 Tandem Arc Connection Diagram...

Страница 16: ...feeder and the Work Sense Lead 21 from the Lead Power Wave AC DC 1000 SD CE Master per guidelines Connect Install welding cables per recommended Output Cable Guidelines see Table1 Output Cable Guideli...

Страница 17: ...English English 14 Paralleling Connection Diagram...

Страница 18: ...feeder and the Work Sense Lead 21 from the Lead Power Wave AC DC 1000 SD CE Master per guidelines Connect Install welding cables to both the master and slave machine per recommended Output Cable Guide...

Страница 19: ...English English 16 MAXsa 19 Connection Diagram...

Страница 20: ...nded Output Cable Guidelines Table 1 Open the Power Wave AC DC 1000 SD CE front panels and configure DIP switch settings per the decal on the panel Factory setting is Master Lead See Figure 2 Connect...

Страница 21: ...ed behind the cover plate on the lower right rear corner Connect the other end of the elec trode cable s to the tab of the contact nozzle Be sure the connection to the nozzle makes tight metal to meta...

Страница 22: ...weld current path For more information regarding the placement of remote work voltage sense leads see the section entitled Voltage Sensing Considerations for Multiple Arc Systems The remote WORK sense...

Страница 23: ...rc starting and low wire driving force wire feeding problems Best results will be obtained when control cables are routed separate from the weld cables This minimizes the possibility of interference b...

Страница 24: ...a total of 3 machines per arc Connections Between Power Sources in Multi Arc Applications K1785 xx Control Cable Synchronizing Connectors are available on the rear panel of the machine for Multi Arc a...

Страница 25: ...fusing information 2 Case Ground Used to provide an earth ground for the frame of the welder Consult your local and national electrical codes for proper grounding information 3 Auxiliary Reconnect Se...

Страница 26: ...ith the Power Wave AC DC 1000 SD CE encompasses a wide range of common processes and will meet most needs If a special welding program is desired contact the local Lincoln Electric sales representativ...

Страница 27: ...ld sequence defines the weld procedure from beginning to end The Power Wave AC DC 1000 SD CE not only provides adjustment of basic welding parameters but also allows the operator to fine tune the star...

Страница 28: ...pt to re establish the arc before it shuts down o A Re strike time of 1 to 2 sec is sufficient in most applications o A Re Strike setting of OFF allows for infinite restriking attempts until a shutdow...

Страница 29: ...d waveforms a phase relationship of 90 should be maintained between adjacent arcs For unbalanced waveforms Avoid switching at same time Break up long periods of unchanged polarity relative to adjacent...

Страница 30: ...ments The calibration procedure itself requires the use of a grid Resistive Load Bank and certified actual meters for voltage and current The accuracy of the calibration will be directly affected by t...

Страница 31: ...he owner of the equipment you should get information on approved collection systems from our local representative By applying this European Directive you will protect the environment and human health...

Страница 32: ...TE this diagram is for reference only It may not be accurate for all machines covered by this manual The specific diagram for a partiuclar code is pasted inside the machine on one of the enclosure pan...

Страница 33: ...ram is for reference only It may not be accurate for all machines covered by this manual The specific diagram for a partiuclar code is pasted inside the machine on one of the enclosure panels If the d...

Страница 34: ...documents related to the integration configuration and operation of the system is available at www powerwavesoftware com Power Wave Submerged Arc Utilities includes the following items and all of the...

Отзывы: