6.4 Fan Control Mode (for ZL-630A) 

*. U43 = 0: Controlled Mode

 

When cooling, if Tpipe < U40, and 

Temp._output

 has run for U41, fan energized; 

If U41 = 0, fan will be energized right after the 

Temp._output 

energized. 

After 

Temp._output

 has de-energized for U42, fan de-energized. 

If U42 = 0, fan will be de-energized right after the 

Temp._output 

de-energized. 

*. U43 = 1: Fan stops during defrosting. At other time, fan works as following 

In cooling mode, during 

Temp._output 

de-energized: 

If U44

0 and U45

0: fan runs for U44, stops for U45, repeatedly, till

 Temp._output 

energized;   

If U44

0 and U45 = 0: fan keeps running;   

If U44 = 0: fan keeps stopping.   

*. U43 = 2: Fan stops during defrosting. At other time, fan keeps running 

*. U43 = 3: Fan runs during defrosting. At other time, fan works as following 

In cooling mode, during 

Temp._output 

de-energized: 

If U44

0 and U45

0: fan runs for U44, stops for U45, repeatedly, till

 Temp._output 

energized;   

If U44

0 and U45 = 0: fan keeps running;   

If U44 = 0: fan keeps stopping.   

*. U43 = 4: Fan runs during defrosting. At other time, fan keeps running also 

 

6.5 Protecting Run When Room Sensor Fails (for Cooling Mode) 

When room sensor fails, 

Temp._output 

will be energized and de-energized periodically. 

For every 30 minutes, 

Temp._output 

will be energized for Trun = U12 * 3 minutes, de-energized for (30 

-Trun) minutes. 

If U12 = 0, no protecting run. 

 

6.6 Run When Pipe Sensor Fails 

When pipe sensor fails, the defrost function will be canceled (for ZL-620A and ZL-630A). 

When pipe sensor fails, and the fan works in controlled mode, fan will be only works according to U41 

and U42 (for ZL-630A).

 

 

6.7 Defrost (for Cooling Mode)   

Defrost Start: 

After 

Temp._output 

energized for U30, and Tpipe < U32, defrost starts.     

Defrost End: 

When Tpipe >

 

U32, or the defrosting has lasted for U31, defrost ends. 

Note: for ZL-610A, only acts according to U30 and U31. 

 

Electrical Defrost (U38 = 0): 

during defrost, 

Temp._output 

de-energized, defrost relay energized. 

Gas or Pump Defrost (U38 = 1): 

during defrost, 

Temp._output 

energized, defrost relay energized.

 

 

Manually Forced Defrost:   

During none-defrost status, keeping

depressed for 7 seconds will start forced defrost; 

During defrost status, keeping

depressed for 7 seconds will stop forced defrost; 

 

 

Содержание ZL-6 0A Series

Страница 1: ...ication Sensor wire 2 meters Sensor NTC R25 5K B25 50 3470K Setting range 40 120 Display range 50 130 Power supply 185 245Vac 50 60Hz Terminal wire 2 1 5mmP 2 or 1 2 5mmP 2 Load 3A 10A 250Vac resistance Storage 30 70 Working 10 45 Working 5 85 RH without dew Case materials PC ABS fire proof Protection level IP65 Front side only Dimension L78 x W34 5 x D71 mm Installation drilling L71 x W29 mm 5 Op...

Страница 2: ...fault settings For example the password will be 1111 5 4 Set Set Point Keep S depressed for 3 seconds to enter into the status Press or to set the value keeping depressed can fast set Press S to exit and save the settings The status will exit without saving if no key operation within 30 seconds 5 5 Set Parameters Password Keep P depressed for 3 seconds digits show 0 Press to select the digit of th...

Страница 3: ...efrost after online 0 180 min 0 disable 0 U38 Defrost type 0 1 0 Electrical 1 Gas or pump 0 U39 Defrost finish sensor 0 1 0 based on timer only 1 based on pipe temperature 1 U40 Fan start temp 45 120 10 U41 Fan start delay 0 600 sec 60 U42 Fan stop delay 0 600 sec 0 U43 Fan control mode 0 4 0 Controlled mode see 6 4 1 Stop in defrosting see 6 4 2 Stop in defrosting else running 3 Run in defrosting...

Страница 4: ..._output forced energized When not defrosting keep depressed for 5 seconds can force Temp _output energized for 30 min During forced cooling keep depressed for 5 seconds will stop forced cooling 6 2 Heating Control If Troom Set point U22 and Temp _output has stopped for U10 then Temp _output energized If Troom Set point and Temp _output has run for U11 then Temp _output de energized Temp _output fo...

Страница 5: ...ing U43 4 Fan runs during defrosting At other time fan keeps running also 6 5 Protecting Run When Room Sensor Fails for Cooling Mode When room sensor fails Temp _output will be energized and de energized periodically For every 30 minutes Temp _output will be energized for Trun U12 3 minutes de energized for 30 Trun minutes If U12 0 no protecting run 6 6 Run When Pipe Sensor Fails When pipe sensor ...

Страница 6: ...ion disappears 8 Over Temp Warning When Troom Set point U50 there will be warning if the following condition meets U50 0 U50 is not set to 0 If power just supplied U53 has passed If defrost just finished U34 has passed The Troom keeps up condition for U52 When Troom Set point U51 there will be warning if the following condition meets U51 0 U50 is not set to 0 If power just supplied U53 has passed ...

Страница 7: ...ive air Installation 1st Insert into drilling hole 2nd Clamp 14 Electrical Wiring Warning Wiring work should be manipulated by certified technicians Supplied power should within specification requirement Sensor and input signal bundles should not be laid together with power supply bundles in same pipe Sensor s bundle is better as short as possible Not wind the redundant length bundle to electrical...

Страница 8: ...Suzhou Lily Tech Co Ltd Page 8 Total 8 Pages Electrical Wiring ...

Отзывы: