Suzhou  Lily  Tech.  Co.,  Ltd. 

                                                                                                                                                                                         
 

Page  2, Total  8  Pages

 

Icon 

Function 

On 

Off 

Blink 

 

Temp. Output 

Energized 

Deenergized 

Delay protecting 

 

Defrost 

Defrosting 

Not defrosting 

Dripping water 

 

Mode 

Cooling mode 

---- 

---- 

 

Mode 

Heating mode 

---- 

---- 

 

Maintenance 

Need maintenance 

No failure found 

---- 

 

Warning 

Has warning 

No warning 

---- 

 
5.3 Digital Display 

Four digits display values in normal condition. They also display warnings as below: 

Warning Code 

Remark 

E01 

Room sensor failure (short or open) 

E02 

Pipe sensor failure (short or open) 

Hi 

Room temp. Is higher than the high limit 

Lo 

Room temp. Is lower than the low limit 

EE 

Memory error 

Err 

Password error 

iA 

External warning 

dEF 

Defrosting 

Frd

 

Forced cooling or heating

 

UnL 

Will restore to 

factory default settings. For example, the password will be “1111” 

 
5.4 Set Set-Point

 

Keep

S

depressed for 3 seconds to enter into the status.   

Press

or

  to set the value

 

(keeping depressed can fast set).   

Press

S

to exit, and save the settings.   

The status will exit without saving, if no key operation within 30 seconds. 

 

5.5 Set Parameters 

Password: 

Keep

P

depressed for 3 seconds, digits show “---0”.   

Press

to select the digit of the password, press

to set the value of the digit.   

press

S

  to confirm.   

If the password is correct, enter into the parameter setting status, else display “Err”, and exit. 

 

Parameter Set: 
The display will show “U10”. Press

or

to select the parameter code (see table below). 

Press

S

  to display the value of the code, press

or

to set its value. 

Press

S

to return. So, all the codes could be set.   

Keep

P

depressed for 3 seconds to exit, and save the settings.   

The status will exit without saving, if no key operation for 30 seconds. 

 

Содержание ZL-6 0A Series

Страница 1: ...ication Sensor wire 2 meters Sensor NTC R25 5K B25 50 3470K Setting range 40 120 Display range 50 130 Power supply 185 245Vac 50 60Hz Terminal wire 2 1 5mmP 2 or 1 2 5mmP 2 Load 3A 10A 250Vac resistance Storage 30 70 Working 10 45 Working 5 85 RH without dew Case materials PC ABS fire proof Protection level IP65 Front side only Dimension L78 x W34 5 x D71 mm Installation drilling L71 x W29 mm 5 Op...

Страница 2: ...fault settings For example the password will be 1111 5 4 Set Set Point Keep S depressed for 3 seconds to enter into the status Press or to set the value keeping depressed can fast set Press S to exit and save the settings The status will exit without saving if no key operation within 30 seconds 5 5 Set Parameters Password Keep P depressed for 3 seconds digits show 0 Press to select the digit of th...

Страница 3: ...efrost after online 0 180 min 0 disable 0 U38 Defrost type 0 1 0 Electrical 1 Gas or pump 0 U39 Defrost finish sensor 0 1 0 based on timer only 1 based on pipe temperature 1 U40 Fan start temp 45 120 10 U41 Fan start delay 0 600 sec 60 U42 Fan stop delay 0 600 sec 0 U43 Fan control mode 0 4 0 Controlled mode see 6 4 1 Stop in defrosting see 6 4 2 Stop in defrosting else running 3 Run in defrosting...

Страница 4: ..._output forced energized When not defrosting keep depressed for 5 seconds can force Temp _output energized for 30 min During forced cooling keep depressed for 5 seconds will stop forced cooling 6 2 Heating Control If Troom Set point U22 and Temp _output has stopped for U10 then Temp _output energized If Troom Set point and Temp _output has run for U11 then Temp _output de energized Temp _output fo...

Страница 5: ...ing U43 4 Fan runs during defrosting At other time fan keeps running also 6 5 Protecting Run When Room Sensor Fails for Cooling Mode When room sensor fails Temp _output will be energized and de energized periodically For every 30 minutes Temp _output will be energized for Trun U12 3 minutes de energized for 30 Trun minutes If U12 0 no protecting run 6 6 Run When Pipe Sensor Fails When pipe sensor ...

Страница 6: ...ion disappears 8 Over Temp Warning When Troom Set point U50 there will be warning if the following condition meets U50 0 U50 is not set to 0 If power just supplied U53 has passed If defrost just finished U34 has passed The Troom keeps up condition for U52 When Troom Set point U51 there will be warning if the following condition meets U51 0 U50 is not set to 0 If power just supplied U53 has passed ...

Страница 7: ...ive air Installation 1st Insert into drilling hole 2nd Clamp 14 Electrical Wiring Warning Wiring work should be manipulated by certified technicians Supplied power should within specification requirement Sensor and input signal bundles should not be laid together with power supply bundles in same pipe Sensor s bundle is better as short as possible Not wind the redundant length bundle to electrical...

Страница 8: ...Suzhou Lily Tech Co Ltd Page 8 Total 8 Pages Electrical Wiring ...

Отзывы: