Suzhou Lily Tech. Co., Ltd.
Page 4, Total 8 Pages
U61 External warning delay
0~120 min
0
●
●
●
U62 Buzzer warning
0~1
0 = disable, 1 = enable
0
●
●
●
U70
Display during defrosting
0~
3
0: Room temperature
1: Room temperature before defrost
2: Set temperature
3
: “dEF”
1
●
●
●
U71
Time to keep defrosting display after
defrost finished
0~
255
min
30
●
●
●
U90 Working mode
CO / HE
CO = cooling, HE = heating
CO
●
●
●
U91 On/offline
On / OFF
On
●
●
●
U99 Password
0000 ~ 9999
1111
●
●
●
6.
Control Function
6.1 Cooling Control
If
Troom
≥
Set-point
+ U22, and
Temp._output
has stopped for U10, then
Temp._output
energized;
If
Troom
≤
Set-point
, and
Temp._output
has run for U11, then
Temp._output
de-energized.
Temp._output
forced energized
When not defrosting,
keep
〖
▼
〗
depressed for 5 seconds can force
Temp._output
energized for 30 min.
During forced cooling,
keep
〖
▼
〗
depressed for 5 seconds will stop forced cooling.
6.2 Heating Control
If
Troom
≤
Set-point
- U22, and
Temp._output
has stopped for U10, then
Temp._output
energized;
If
Troom
≥
Set-point
, and
Temp._output
has run for U11, then
Temp._output
de-energized.
Temp._output
forced energized
When not in setting status, and
Temp._output
de-energied,
keep
〖
▼
〗
depressed for 5 seconds can
force
Temp._output
energized.
During forced heating,
keep
〖
▼
〗
depressed for 5 seconds will stop heating.
6.3
Temp._output delay protection
After power supply,
Temp._output
could be energized after U10;
After
Temp._output
de-energized, it could be energized again after U10;
After
Temp._output
energized, it could be de-energized after U11.