XAC80 Profibus-DP
®
5.2 Connection cap with PG gland (cable output)
Figure 2 - Connection cap
The connection cap is fitted with three PG9 cable glands for BUS IN and BUS
OUT connections and power supply connection. The bus cables can be connected
directly to the terminal connectors located in front of each cable gland.
We recommend Profibus-DP certified cables to be used. Core diameter should
not exceed Ø 1.5 mm (0.06 inches). Please note that BUS IN and BUS OUT
connections are actually the same and so interchangeable.
Terminal connector
Description
-
0Vdc Supply voltage
+
+10Vdc +30Vdc Supply voltage
B
Profibus B (Red)
A
Profibus A (Green)
PG
Shield
1
1
Connect the cable shield to cable gland
5.3 Ground connection
Minimize noise by connecting the shield and/or the encoder frame to ground
(GND). Make sure that ground (GND) is not affected by noise. The connection
point to ground can be situated both on the device side and on user's side. The
MAN XAC80 PB E 1.0.odt
5 - Electrical connections
28 of 60