SMAX MODBUS®
Value
Baud rate
Parity bit
00 hex
9600 bit/s
No parity
01 hex
9600 bit/s
Even
02 hex
9600 bit/s
Odd
03 hex
19200 bit/s
No parity
04 hex (default)
19200 bit/s
Even
05 hex
19200 bit/s
Odd
06 hex
115200 bit/s
No parity
07 hex
115200 bit/s
Even
08 hex
115200 bit/s
Odd
Control Word [000A hex]
[Register 11, Unsigned16, rw]
This variable contains the commands to be sent in real time to the Slave in order
to manage it.
Byte structure of the
register:
byte
MSB
LSB
bit
15
…
8
7
…
0
msb
lsb
msb
lsb
Byte 0
Not used.
Byte 1
Watchdog enable
bit 8
Watchdog function to be enabled; setting the
bit to “=0” causes the Watchdog function to be
disabled. When the Watchdog function is enabled, if the
device does not receive any message from the Server within
1 second, the system forces an alarm condition (the
alarm is invoked to appear as soon as the
Modbus network communication is restored). Watchdog
function is a safety timer that uses a time-out to detect
loop or deadlock conditions. For instance, should the serial
communication be cut off while a command is still active
and running Watchdog safety system immediately takes
action and commands an alarm to be triggered.