RD4 CANopen®
4.4.2 Setting the data transmission rate: Baud rate (Figure 4)
WARNING
Power supply must be turned off before performing this operation!
Set the hexadecimal value of the transmission rate according to the following
table.
Available baud rate values:
Data byte
Baud rate
00h
20 Kbit/s
01h
50 Kbit/s
02h
100 Kbit/s
03h
125 Kbit/s
04h
250 Kbit/s
05h (default)
500 Kbit/s
06h
800 Kbit/s
07h
1000 Kbit/s
4.4.3 RT bus termination (Figure 4)
A bus termination resistor is provided and has to be activated as line
termination in the last device of the transmission line.
Use RT Switch to activate or deactivate the bus termination.
RT
Description
1 = 2 = ON
Activated: when the device is at the end of
the transmission line
1 = 2 = OFF
Deactivated: when the device is not at the end
of the transmission line
MAN RD4 CB E 1.5
Electrical connections
23 of 72