RD4 CANopen®
03
Inhibit Time
[Unsigned16, rw]
Minimum interval between two PDO transmissions when “status,
position, velocity exchange” transmission is set (see the parameter
Transmission Type
object 1800h sub 2 and the NOTE just below); value
is expressed in multiples of 100 µs.
Default = 0190h (40ms)
NOTE
- Before altering the value of
COB-ID
it is compulsory to deactivate the
transmission of PDO1, then enter the new COB-ID value, finally activate again
the transmission of PDO1.
- PDO1 transmission can be activated (deactivated) by setting to “0” (“1”) the
most significant bit of the object
1800 Transmit PDO Communication
sub 1
COB-ID
.
- Cyclic transmission or synchronous transmission can be modified by setting a
1800 Transmit PDO Communication Parameter
Transmission Type
. To have a PDO1 transmission every “n” SYNC
commands, set “n” value in the object 1800h, sub 2.
01h = synchronous transmission at every SYNC command
02h = synchronous transmission every two SYNC commands
…
FEh = “cyclic transmission” or “status, position, velocity exchange
transmission”:
≠
0
“cyclic transmission”: cycle time is set in
“status, position, velocity exchange”
transmission: device issues a PDO message each time parameters
mapped in PDO change (see object
with a minimum interval not lower than
sub 3
Inhibit Time
.
1A00 TPDO Mapping Parameter 1
This object indicates the kind of parameter contained in the Transmit PDO
message.
01
[Unsigned32, ro] Default = 3101 0010h.
02
3105-00 Current velocity value
[Unsigned32, ro] Default = 3105
0010h.
03
3103-00 Current position value
[Unsigned32, ro] Default = 3103
0020h.
MAN RD4 CB E 1.5
Programming parameters
53 of 72