EM58 – HS58 - HM58 MODBUS TCP/IP
Alarm registers [121-122]
[120-121, Unsigned16, ro]
Bit
Function
bit = 0
bit = 1
0 … 11
not used
12
Alarm not active
Alarm active
13
Alarm not active
Alarm active
14
Alarm not active
Alarm active
15 … 31
not used
These registers are meant to show the alarms currently active in the device. An
alarm will be set if a malfunction in the encoder could lead to incorrect position
value. If an alarm occurs, the according bit is set to logical high (1) until the
alarm is cleared and the encoder is able to provide an accurate position value.
The available alarm messages are described here afterwards.
Byte 0
Not used.
Byte 1
bits 8 … 11
Not used.
Machine data not valid
bit 12
One or more parameters are not valid, set proper values to
restore normal work condition. See the list of the wrong
parameters in the
Wrong parameters list [125-126]
registers.
Setting data not valid
bit 13
This alarm message is currently disabled in this firmware
version.
Flash memory error
bit 14
Flash memory internal error, it cannot be restored (bad
checksum error, etc.).
bit 15
Not used.
Bytes 2 and 3
Not used.
NOTE
Please note that should the alarm be caused by wrong parameter values (see
Wrong parameters list [125-126]
normal work status can be restored only after having set proper values. The
alarm cannot be reset.
MAN EM58_HS58_HM58 MT E 1.1.odt
Programming parameters
64 of 104