Key
Features
•
The Dehumidistat measures the indoor humidity level and
will initiate high speed ventilation when the moisture level
in the building exceeds the set point on the control.
•
Once the humidity in the building is reduced, the HRV will
revert back to its previous setting.
•
The Dehumidistat should be set to OFF for all season
except the heating season.
•
Connect to 3 wire 20 gauge low voltage wire.
Humidity
Control
Humidity is controlled through the adjustable Dehumidistat
(included with the pool HRV). The Dehumidistat should be wall
mounted in an accessible location of the pool room about 5 feet
above floor level. The operator should set the Dehumidistat dial
at an acceptable humidity level (40% to 50% RH). The pool HRV
will enter ventilation mode when the pool room's humidity level
exceeds the Dehumidistat set point.
The pool HRV will revert to recirculation with no outside air
entering the system when the indoor humidity level falls below
the Dehumidistat set point.
Setting
the
Dehumidistat
Press and release the Dehumidistat button until the
Dehumidistat Light is at the desired setting. After 5 seconds the
Dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the
setting and the unit is operating on high speed ventilation. A
continuous light indicates the humidity level is lower than the
setting. Refer to the unit's Operation & Installation Manual for
instructions on how the Dehumidistat works.
Note
- Only 1 Dehumidistat should be active on a system.
Lifebreath
Dehumidistat
-
Part
#99
-D
H01
Included
%
80
20
Instruction card
Dehumidistat
Indicator
LEDs
Set to the desired
humidity level. High
speed ventilation will
initiate when the indoor
moisture level exceeds
the set point on the
control.
Dehumidistat
Adjust button
17
Optional Lifebreath 3 Speed Control - Part #99-500
HIGH
OFF
OFF
OFF
MED
LOW
•
3 Speed Fan setting (LOW / MEDIUM / HIGH)
•
4 wire; 20 gauge wire (minimum)
•
Connect to Red, White, Yellow, Green.
ATTENTION
When used in conjunction with t
he 99-BC02
,
the
BC02 c
ontrol must be ON for the 99-500
c
ontrol
to operate. The 99-BC02 will override the
99-500
c
ontrol when the Dehumidistat is
operating or the control is set to HIGH speed.
Key Features: