Communication Interfaces
80
Group 3:
User
Settings
1
SCR1 Fast Undervoltage
Setpoint
Integer
In % of nominal below nominal
2
SCR1 Slow Undervoltage
Setpoint
Integer
In % of nominal below nominal
3
SCR1 Slow Undervoltage
Detect Delay
Integer
In number of lines cycles
4
SCR1 Overvoltage
Setpoint
Integer
In % of nominal above nominal
5
SCR1 Overvoltage Detect
Delay
Integer
In 1/4 lines cycles
6
SCR1 I peak Transfer
Setpoint
Integer
x 10
7
SCR2 Fast Undervoltage
Setpoint
Integer
In % of nominal below nominal
8
SCR2 Slow Undervoltage
Setpoint
Integer
In % of nominal below nominal
9
SCR2 Slow Undervoltage
Detect Delay
Integer
In number of lines cycles
10
SCR2 Overvoltage
Setpoint
Integer
In % of nominal above nominal
11
SCR2 Overvoltage Detect
Delay
Integer
In 1/4 lines cycles
12
SCR2 I peak Transfer
Setpoint
Integer
x 10
13
Max. Transfer Phase
Angle
Integer
In degrees
14
Output Frequency
Deviation
Integer
Freq. in Hz x 10
15
ReTransfer Delay Time
Integer
In seconds
16
Horn Volume
Integer
Range: 1-10
17
Critical Option Enabling
Bitpacked
See section
12.1.3
.
18
Non-Critical Option
Enabling
Bitpacked
See section
12.1.3
.
Group 4:
Event Mask
Settings
1 to
63
Event Mask settings for
faults
Event Mask
See section
12.1.4
.
64 to
143
Event Mask settings for
alarms
Event Mask
See section
12.1.4
.
Table 11
Group settings and values (continued)
Group
Item:
Description
Value Type
Value Notes