Power and Control Wiring
11
For preparation purposes, the following tables provide the dimensions and wire sizes for the input
junction boxes.
Table 3
Input junction box dimensions
Switch Rating
Length
Inches (mm)
Width
Inches (mm)
Height
Inches (mm)
100 amp
16 (406)
14 (356)
6 (152)
250 to 600 amp
30 (762)
16 (406)
6 (152)
Table 4
Input junction box terminal wire size range
Switch Rating
Power and Ground Lug Wire Range
100 amp
#6 to #2/0 AWG
250 to 600 amp
(2) #6 AWG to (2) 500 kcmil
Содержание STS2
Страница 2: ......
Страница 27: ...Installation Drawings 19 Figure 6 Outline drawing 400 600 amp Liebert STS2 PS211400 Rev 02...
Страница 28: ...Installation Drawings 20 Figure 7 Outline drawing 800 1000 amp Liebert STS2 PS211800 Rev 02...
Страница 149: ...Maintenance 141 Channel 8 Channel 9 Channel 10 PRB Notes...
Страница 151: ......