Alarm and Faults
75
084
CB1 (S1) OPEN
Source 1, Circuit Breaker 1 is open.
A, E
085
CB2 (S2) OPEN
Source 2, Circuit Breaker 2 is open.
A, E
086
CB4 (S1 BYP) CLOSED
Source 1 on bypass, Circuit Breaker 4 is closed.
A, E
087
CB5 (S2 BYP) CLOSED
Source 2 on bypass, Circuit Breaker 5 is closed.
A, E
088
CB3 (OUTPUT) OPEN
Output circuit breaker (CB3) is open.
A, E
089
CB3A (OUTPUT) OPEN
Output circuit breaker (CB3A) is open.
A, E
090
S1 PHASE ROT ERROR
Source 1 phase rotation error.
A, E
091
S2 PHASE ROT ERROR
Source 2 phase rotation error.
A, E
092
TRANSFER INHIBITED
Transfer inhibited.
A, E
093
OUTPUT UV
Output is under voltage.
D, F, A, E
120
121
122
123
124
125
126
127
INPUT CONTACT #1
INPUT CONTACT #2
INPUT CONTACT #3
INPUT CONTACT #4
INPUT CONTACT #5
INPUT CONTACT #6
INPUT CONTACT #7
INPUT CONTACT #8
Input Contact #
x
is an optional alarm input. The alarm name
can be programmed with an alarm name from the Input
Contactor Isolator settings option under the Comm Options.
See
Configuring the Input Contact Isolator Settings on
page 95
. The alarm is sent to Monitor DSP. The LCD logs the
alarm with the programmed name. Monitor DSP logs it with the
generic name which is how it is reported to the SVT query.
A, E
128
CONFIG MODIFIED
A set point configuration has changed.
A, E
129
PASSWORD CHANGED
The password for touch screen access has been modified and
saved.
A, E
130
TIME REPROGRAMMED
The system’s time has been reset and saved.
A, E
131
DATE REPROGRAMMED
The system’s date has been reset and saved.
A, E
132
EVENT LOG CLEARED
The event log has been erased.
A, E
133
HIST LOGS CLEARED
Both History Logs have been erased.
A, E
134
HIST LOGS FULL
Both History Logs have been written and no more history logs
can be written without clearing one of the logs.
A, E
Table 8
Event messages (continued)
ID
Alarm Message
Description/Cause
Action