Specifications
22
Table 8
Liebert PSI XR battery run times
Number of
Batteries
Load %
1000VA
1500VA
2200VA
3000VA
Internal Battery
10
82
81
76
75
25
43
32
32
32
50
15
13
14
13
75
9
8
8
8
100
6
5
5
5
Internal Battery
+ 1 External
Battery Cabinets
10
272
222
161
142
25
139
109
80
70
50
73
55
45
31
75
51
31
25
17
100
31
18
15
12
Internal Battery
+ 2 External
Battery Cabinets
10
438
357
241
205
25
231
175
128
106
50
129
95
67
56
75
84
61
47
31
100
65
46
29
18
Internal Battery
+ 3 External
Battery Cabinets
10
614
492
322
267
25
324
241
170
139
50
181
131
95
73
75
126
84
62
50
100
96
64
48
31
Internal Battery
+ 4 External
Battery Cabinets
10
789
627
483
329
25
385
308
255
171
50
233
167
143
95
75
162
114
100
62
100
124
82
72
47
Internal Battery
+ 5 External
Battery Cabinets
10
964
762
564
392
25
509
374
298
204
50
285
203
167
113
75
197
139
116
74
100
151
106
84
56
Internal Battery
+ 6 External
Battery Cabinets
10
1140
897
644
454
25
601
440
341
236
50
336
239
191
131
75
233
163
133
85
100
179
124
102
65
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.