background image

1

I

MPORTANT

 S

AFETY

 I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that must be followed during the installation and 
maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or 
operate this UPS. 

The equipment can be installed and operated by individuals without previous training.

Battery Handling Precautions

!

WARNING

Install the UPS indoors in a temperature- and humidity-controlled room, free of conductive 
contaminants, moisture, flammable liquids, gases and corrosive substances.
Some components are live, even when AC power is disconnected. For service, contact a 
properly trained and qualified technician. Do not remove the cover; the UPS has no 
user-serviceable parts inside except the internal battery pack.
Operate the UPS only from a properly grounded (earthed) 220-240 VAC, 50Hz or 60Hz AC 
supply. Do not supply this UPS from electrical power systems of the IT type 
(IEC 364 - Electrical Installation of Buildings).

!

WARNING

Although the UPS has been designed and manufactured to ensure personal safety, improper 
use can result in electrical shock or fire. To ensure safety, observe the following rules:
• Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use 

liquid or aerosol cleaners.

• Do not install or operate the UPS in or near water.
• Never block or insert any objects into the ventilation holes or other openings of the UPS. 

Keep all vents free of dust accumulation that could restrict air flow.

• Do not place UPS power cord anywhere it might be damaged.

!

WARNING

Batteries should be replaced only by properly trained and qualified personnel knowledgeable 
of batteries and required precautions.
A battery can present a risk of electrical shock and high short-circuit current. The following 
precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause 

injury to the skin and eyes.

• When replacing the battery, use the type of battery as is listed in 

Tables 6

 and

7

.

• Handle, transport and recycle batteries in accordance with local regulations.

“«ˆVœ˜°Vœ°ÕŽÊ

ÊÊÊÊÊ/Ê>˜`ʘÃÌÀՓi˜Ì>̈œ˜ÊvœÀʈ˜`ÕÃÌÀÞ

->iÃ\

Ê

³{{Ê­ä®Ê£ÓÇÎÊxÇäÊÓÓäÊÊÊ

7iLÈÌi\

ÊÜÜÜ°>“«ˆVœ˜°Vœ°ÕŽÊÊÊ

“>ˆ\

ÊÃ>iÃJ>“«ˆVœ˜°Vœ°ÕŽÊÊ

Liebert UPS user manual

Содержание PS1000RT3-230XR

Страница 1: ...AC Power For Business Critical Continuity Liebert PSI XR User Manual 1000 1500 2200 3000VA 50 60Hz 230VAC V V i v i x 7iL i V V i J V V Liebert UPS user manual...

Страница 2: ...V V i v i x 7iL i V V i J V V BLANK PAGE Liebert UPS user manual...

Страница 3: ...anual Self Diagnostic Test 14 4 1 2 Off Button 14 4 2 Status Indicators 14 4 2 1 Status Change Button 14 4 2 2 Load Level Indicator 14 4 2 3 Battery Level Indicator 15 4 2 4 UPS Status Indicators 15 5...

Страница 4: ...ace port 10 Figure 12 EPO connection for normally open operation 11 Figure 13 Install the external battery cabinet in tower installation 11 Figure 14 Connect battery cabinets to UPS 12 Figure 15 Displ...

Страница 5: ...al safety improper use can result in electrical shock or fire To ensure safety observe the following rules Turn Off and unplug the UPS before cleaning it Clean the UPS with a dry cloth Do not use liqu...

Страница 6: ...or if you are unsure then convert the input cable attachment to either a fixed wiring installation or an industrial plug socket e g CEE 17 connector This alteration should be carried out by a properly...

Страница 7: ...tant instructions Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Alarm Silence Manual Self Diagnostic T...

Страница 8: ...ower Liebert PSI XR tower configuration Display rotates for use in rack DC 24V EPO INPUT OUTPUT VOLTAGE 220V VOLTAGE 230V VOLTAGE 240V 2 1 FUNCTION RJ 45 Data Line Connectors USB Port RS 232 DB 9 Port...

Страница 9: ...IEC Output Cable 2200 3000 only 3 Tower Stand Rack Mount Handles Battery UPS Tab Figure 4 Accessories Mounting Hardware Screws Washers Liebert Shutdown Software Program Liebert Shutdown Software CD U...

Страница 10: ...unit away from water flammable liquids gases corrosives and conductive contaminants see Figure 5 Maintain a minimum clearance of 305mm 12 inches in the front and rear of the UPS Maintain an ambient t...

Страница 11: ...7 3 2 Tower UPS Installation See Figure 6 when using the Liebert PSI XR in a tower configuration Figure 6 Tower configuration attach Tower Stand Step 1 Step 2 V V i v i x 7iL i V V i J V V Liebert UPS...

Страница 12: ...the UPS into and out of the rack WARNING Risk of top heavy unit falling over May cause equipment damage personal injury or death Placing heavy equipment near the top of a rack may increase the risk of...

Страница 13: ...onnect Input Power and Load The 1000VA and 1500VA models do not include an input power cable the 2200VA and 3000VA UPSs include an input power cable Connect input power to the UPS then plug the equipm...

Страница 14: ...any of these communication methods serial contact closure USB SNMP See the Liebert shutdown software installation guide on the included CD ROM for details and instal lation information Also refer to 6...

Страница 15: ...the external battery cabinet in a tower configuration or in a rack see Figure 13 or 3 3 Rack Mount UPS Conversion and Installation 3 Connect the external battery cabinet cable to the rear of the exter...

Страница 16: ...tor color key UPS Model Nominal System Voltage connector color External Battery Cabinet Model PS1000RT3 230XR 24VDC Red PSRT3 24VBXR PS1500RT3 230XR PS2200RT3 230XR 48VDC Gray PSRT3 48VBXR PS3000RT3 2...

Страница 17: ...LED 3 Battery Condition Battery Fault Weak 4 LED 4 Grounding Site Wiring Fault UPS Grounding Site Wiring Fault 5 LED 5 Overload UPS Overload 1 to 5 Load Battery Level Indicate Load Battery Level 6 Sta...

Страница 18: ...merson representative or Liebert Applications If LED indicates a UPS Fault Remove the load retest the self diagnostic test if LED indicated UPS Fault Contact your local dealer Emerson representative o...

Страница 19: ...ery When the UPS battery voltage is low the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning Site Wiring Fault In case of a site wiring faul...

Страница 20: ...zing the batteries 5 3 Battery Mode The UPS switches to Battery Mode in the event of an extreme input voltage frequency condition or mains failure When the UPS is in Battery Mode the Battery Indicator...

Страница 21: ...rt is removed the UPS output can be enabled by pressing the ON Alarm Silence Manual Self Diagnostic Test button 6 2 2 Battery Mode Shutdown Via Pins 4 5 While the UPS is operating on battery a 5 12VDC...

Страница 22: ...onfigurations A two pin DIP switch on the rear of the Liebert PSI XR permits setting the UPS to operate at nominal voltages of 220V 230V or 240V This feature will change the high and low points at whi...

Страница 23: ...e of the front bezel 2 Pull the front bezel off the UPS 3 Remove the two screws on the battery bracket 4 Remove the screw on the battery connectors holder 5 Disconnect the two slotted red gray and bla...

Страница 24: ...VAC configurable Voltage Battery Mode 220 230 240 VAC configurable 5 before low battery warning Transfer Time 4 6 ms typical On Battery Waveform Sinewave Overload Warning 100 Overload Shutdown Normal...

Страница 25: ...eries Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 8 x 12 x 7 2 8 x 12 x 7 2 Battery Manufacturers CSB YUASA or Equivalent Environmental Operating Temperature C F 0 to 40 32...

Страница 26: ...l Battery Cabinets 10 614 492 322 267 25 324 241 170 139 50 181 131 95 73 75 126 84 62 50 100 96 64 48 31 Internal Battery 4 External Battery Cabinets 10 789 627 483 329 25 385 308 255 171 50 233 167...

Страница 27: ...atteries UPS starts on battery but will not switch to AC dark start UPS not plugged in Plug in the power cord securely Circuit breaker tripped Reset the circuit breaker AC overvoltage Wait until volta...

Страница 28: ...Troubleshooting 24 Notes V V i v i x 7iL i V V i J V V BLANK PAGE Liebert UPS user manual...

Страница 29: ...V V i v i x 7iL i V V i J V V BLANK PAGE Liebert UPS user manual...

Страница 30: ...tion assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2008 Liebert Corporation All rights reserved throughout the...

Отзывы: