Specifications
20
8.0
S
PECIFICATIONS
Table 6
Liebert PSI XR specifications
Model Number
PS1000RT3-230XR
PS1500RT3-230XR
PS2200RT3-230XR
PS3000RT3-230XR
Power Rating, VA/W
1000VA/900W
1500VA/1350W
2200VA/1980W
3000VA/2700W
Dimensions, W x D x H, mm (in)
Unit
440 x 490.5 x 88
(17.3 x 19.3 x 3.5)
440 x 490.5 x 88
(17.3 x 19.3 x 3.5)
440 x 700.5 x 88
(17.3 x 27.6 x 3.5)
440 x 700.5 x 88
(17.3 x 27.6 x 3.5)
Shipping
560 x 612 x 228
(22 x 24.1 x 9)
560 x 612 x 228
(22 x 24.1 x 9)
560 x 821 x 228
(22 x 32.3 x 9)
560 x 821 x 228
(22 x 32.3 x 9)
Weight, kg (lb)
Unit
25 (55)
28 (61)
42 (93)
46 (102)
Shipping
29 (64)
32 (70)
47 (104)
51 (111)
Input AC Parameters
Surge Protection
220J
Voltage Range
Without Battery Operation
165 to 300 VAC (configurable)
Frequency Range
45~65Hz, (±0.5Hz)
Input Socket
IEC-320-C14
IEC-320-C14
IEC-320-C20
IEC-320-C20
Output Sockets
(6) IEC-320-C13
(6) IEC-320-C13
(6) IEC-320-C13
(1) IEC-320-C19
(6) IEC-320-C13
(1) IEC-320-C19
Voltage (Normal Mode)
220/230/240 VAC (configurable)
Voltage (Battery Mode)
220/230/240 VAC (configurable); ±5% before low-battery warning
Transfer Time
4-6 ms typical
On-Battery Waveform
Sinewave
Overload Warning
>100%
Overload Shutdown
(Normal Mode)
>120%, shutdown after one cycle (normal mode).
Overload Shutdown
(Battery Mode)
>130%, shutdown after one cycle (normal mode).
Battery Parameters
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating
4 x 12 x 7.2
4 x 12 x 9
8 x 12 x 7.2
8 x 12 x 9
Recharge Time
5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load
5 min.
Half Load
10 min.
Environmental
Operating Temperature, °C (°F)
0 to 40 (32 to 104)
Storage Temperature, °C (°F)
-15 to 40 (5 to 104)
Relative Humidity
0% to 90%, non-condensing
Operating Altitude
Up to 3000m (10,000 ft) at 35°C (95°F) without derating
Audible Noise
<40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety
IEC62040-1-1
EMC
IEC/EN/AS 62040-2 2nd Ed Class A
Transportation
ISTA Procedure 1A Certification
Battery backup times are approximate and may vary depending on the load and battery charge.
«V°V°ÕÊ
ÊÊÊÊÊ/Ê>`ÊÃÌÀÕiÌ>ÌÊvÀÊ`ÕÃÌÀÞ
->iÃ\
Ê
³{{Êä®Ê£ÓÇÎÊxÇäÊÓÓäÊÊÊ
7iLÃÌi\
ÊÜÜÜ°>«V°V°ÕÊÊÊ
>\
ÊÃ>iÃJ>«V°V°ÕÊÊ
Liebert UPS user manual