Installation
6
3.0
I
NSTALLATION
3.1
Preparation
Inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Emer-
son representative.
The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method
that suits the application and proceed.
Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi-
ronment. Place it in an area with unrestricted airflow around the unit, away from water, flammable
liquids, gases, corrosives and conductive contaminants (see
Figure 5
).
Maintain a minimum clearance of 305mm (12 inches) in the front and rear of the UPS. Maintain an
ambient temperature range of 0°C to 40°C (32°F to 104°F) (see
Figure 5
).
Figure 5
Placing the Liebert PSI XR
!
CAUTION
Risk of injury from heavy unit. May cause equipment damage or personal injury.
The UPS and battery cabinets are heavy (see
Table 6
and
Table 7
). Take proper precautions
when lifting or moving either the UPS or battery cabinets.
0°C (32°F)
Relative humidity
(non-condensing)
40°C (104°F)
0% ~ 90%
305mm/12inch
AIR
AIR
AIR
«V°V°ÕÊ
ÊÊÊÊÊ/Ê>`ÊÃÌÀÕiÌ>ÌÊvÀÊ`ÕÃÌÀÞ
->iÃ\
Ê
³{{Êä®Ê£ÓÇÎÊxÇäÊÓÓäÊÊÊ
7iLÃÌi\
ÊÜÜÜ°>«V°V°ÕÊÊÊ
>\
ÊÃ>iÃJ>«V°V°ÕÊÊ
Liebert UPS user manual