pag. 12
Tab. 4 -- 50 Hz Technical data for ”COOLING ONLY” and “C HEATING” unit versions
(F and F+C) coupled with “HPSCxxA/L”
Model
HPS 06
HPS 08
HPS 10
HPS 12
HPS 14
Operating limits
Main power supply voltage
230V ±10%
/ 1Ph / 50Hz
400V ±10% / 3Ph+N+PE / 50Hz
Outdoor conditions
(*)
from:
---30
°
C
Outdoor conditions
(*)
to:
51
°
C
50
°
C
from:
24
°
C, 30% R.H / 80% R.H.
(**)
Indoor conditions with compressor running
to:
34
°
C,
40% R.H.
30
°
C, 40% R.H.
Storage conditions
from:
---40
°
C, 5% R.H.
Storage conditions
to:
55
°
C, 90% R.H.
Sound pressure level
Outdoor sound pressure level
(1)
dB(A)
48.5
48.5
52.5
53.5
55.0
Indoor sound pressure level
dB(A)
58.0
62.5
62.5
64.0
64.0
Standard electrical features
Compressor --- AC power input
(2)
kW
1.73
2.23
3.06
3.75
4.68
Compressor --- AC operative current (OA)
(2)
A
8.0
4.0
5.5
6.6
8.6
Compressor --- AC max. current (FLA)
A
11.4
5.1
7.0
10.0
10.2
Compressor --- AC starting current (LRA)
A
47.0
32.0
46.0
50.0
63.0
Condenser fan --- AC power input
(2)
kW
0.07
0.10
0.22
0.22
0.28
Condenser fan --- AC max. power input
kW
0.24
0.24
0.48
0.48
0.48
Condenser fan --- AC operative current (OA)
(2)
A
0.6
0.7
1.5
1.5
1.7
Condenser fan --- AC max. current (FLA)
A
1.4
1.4
2.8
2.8
2.8
Condenser fan --- AC max. current (FLA)
A
1.6
1.6
3.3
3.3
3.3
Evaporator fan --- AC power input
(2)
kW
0.18
0.35
0.35
0.34
0.34
Evaporator fan --- AC operative current (OA)
(2)
A
0.8
1.5
1.5
2.0
2.0
Evaporator fan --- AC max. current (FLA)
(3)
A
1.0
2.0
2.0
2.0
2.0
Evaporator fan --- AC starting current
A
1.3
2.7
2.7
2.7
2.7
Electric heating (optional)
Heating capacity
kW
1.5
3.0
3.0
4.5
6.0
Heating --- max. current
A
6.5
13.0
OA:
Standard Operating Ampère
FLA:
Full Load Ampère
LRA:
Locked Rotor Ampère
Notes:
(*)
Maximum outdoor temperature referred to 30
û
C / 35% R.H. indoor unit air suction (HPSE).
(**)
Conditions referred to the suction sections of the inner unit (HPSE); the min. indoor temperature is referred to 30% of indoor relative humidity and to the min.
outdoor temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is higher than the table data.
(1)
Measured with 35
û
C outdoor temperature at 2m far from the unit; free field conditions.
(2)
Indoor reference conditions: 30
û
C / 35% R.H. at the HPSE indoor unit air suction sides; 35
û
C outdoor. Nominal power supply.
(3)
It refers to nominal speed (Factory setting).