background image

Vertiv

|

Liebert

®

 EXM

 BDC User Manual  |  Rev. 3  |  01/18  |

42

Содержание EXM BDC

Страница 1: ...Liebert EXM BDC User Manual 10 100kVA 60Hz...

Страница 2: ......

Страница 3: ...Liebert EXM BDC with optional internal transformer Typical configuration 6 Figure 2 Liebert EXM BDC Access plate removed 7 Figure 3 Accessory fuses 9 Figure 4 Liebert EXM BDC with distribution single...

Страница 4: ...for Liebert EXM to Liebert EXM BDC 8 Table 2 Liebert EXM BDC interface 17 Table 3 Output dry contact relays 19 Table 4 Wiring for Liebert EXM to Liebert EXM BDC 27 Table 5 Hardware torque values 27 T...

Страница 5: ...he cabinet before transporting it Never tilt equipment more than 15 degrees from vertical In case of fire involving electrical equipment use only carbon dioxide fire extinguishers or those approved fo...

Страница 6: ...sants sous tension sont abrit es derri re un panneau m tallique D autres crans de s curit internes prot gent l quipement en conformit avec les normes IP20 Ne retirez jamais les panneaux ou les couverc...

Страница 7: ...required for procedures involving handling installation and maintenance of the UPS system and the internal batteries internal batteries accommodated by the 10 40kVA frame only Observe all safety preca...

Страница 8: ...cautions de s curit sp ciales sont requises pour les proc dures associ es la manutention l installation et l entretien du syst me ASC Observez toutes les pr cautions de s curit d crites dans le pr sen...

Страница 9: ...ectrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle D...

Страница 10: ...mode MBB closed BIB MIB open it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair In this mode of operati...

Страница 11: ...a qualified certified electrician Removing the Cover Plates Plates cover the input and output terminals on the front of the Liebert EXM BDC see Figure 2 Remove these and keep the screws and plates fo...

Страница 12: ...s between the Liebert EXM BDC UPS Output Busbars A B C N terminals and UPS output busbars A B C N terminals and tighten the connections to 428 lb in 48Nm for M12 bolt 9 Connect TB1 from the Liebert EX...

Страница 13: ...provides 120V and is connected to the UPS output L N The fuse is rated for 8A Figures 4 5 and6 show the back feed breaker wiring the connections are made to the static bypass assembly as shown in Tabl...

Страница 14: ...BDC is connected to the UPS module all control and power wiring is supplied by Vertiv When the Liebert BDC is remote from the UPS module the cables between the Liebert BDC and UPS module must be supp...

Страница 15: ...B W07 W08 W09 W04 W05 W06 Detail A Detail B DETAIL A DETAIL B 607509 Pg 1 Rev 3 W88 UPS Fuse W89 W90 AC Output AC Input Ground to Unit Frame Utility Input TB1 MBB Output Neutral Ground Neutral W85 W83...

Страница 16: ...y or Field Supplied Customer Input Neutral Customer Main Ground Busbar Ground Electrode See Note 2 Isolation Transformer BIB W07 W08 W09 W04 W05 W06 Detail A Detail B To Panelboard or Subfeed DETAIL A...

Страница 17: ...o P8 Ribbon Cable to P9 Ribbon Cable to P15 CT STRIP 1 CT STRIP 2 50 Pin 50 Pin 50 Pin 50 Pin LEFT SIDE RIGHT SIDE Rear View Rear View P16 50 Pin P15 50 Pin P8 50 Pin P9 50 Pin Pin 1 Pin 1 W508 Black...

Страница 18: ...9 to Accent 607740 Pg 5 Rev 2 P16 50 Pin P38 34 Pin P15 50 Pin P8 50 Pin P9 50 Pin Pin 1 Pin 1 552454P2 552454P2 536952G2 53694P1 53834G1 Load Line C Phase B Phase A Phase C Phase B Phase A Phase Fuse...

Страница 19: ...rted from either the UPS side or from the Liebert EXM BDC side whichever is more convenient NOTE UPS wiring must be completed before the cabinets are bolted together A DETAIL A Washer Flat M10 Washer...

Страница 20: ...The Liebert EXM BDC and battery cabinets must be properly prepared and secured for lifting Improper lifting may cause the cabinets to fall causing equipment damage personal injury and death Vertiv rec...

Страница 21: ...Main input switch status signal J26 5 Q2 STA Bypass input switch status signal J26 9 Q3 STA External maintenance switch status signal J26 3 7 9 GND Ground for dry contacts These contacts cannot be act...

Страница 22: ...iebert EXM BDC wiring J26 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 GEN MODE 12V_DRY GND_DRY GND_DRY TMP BATT IN _ RESERVED ENV_DET GND_DRY CHG SHUT GND_DRY RESV1 UT2 485 UT2 485 GND_DRY NC NC 1 3 5...

Страница 23: ...en the inverter is abnormal 4 INV_S Inverter state common contact 6 INV_C Inverter state normally open contact Closed when the inverter is normal J23 1 BFP_O Bypass back feed normally open contact Ope...

Страница 24: ...nel Removed 78 5 1994mm MBB Panelboard MIB BIB System Input Bus Ground Bus Neutral Bus 23 6 600mm 37 5 953mm NOTES 1 Dimensions are in inches mm 2 Control wiring and power wiring must be run in separa...

Страница 25: ...only are recommended 4 All wiring is to be in accordance with national and local electrical codes 5 When the Liebert EXM BDC is attached to the UPS Vertiv will supply the interconnection cables 6 225A...

Страница 26: ...XM BDC with optional SKRU and transformer Key Operator Lamp Kirk Keys MBB BIB MIB System Input Bus LDB Transformer Option for 208V 220V 480V or 600V Input Neutral Bus Ground Bus EXM15007 Rev 0 FRONT V...

Страница 27: ...n in separate conduits 3 All wiring is to be in accordance with national and local electrical codes 4 Vertiv will supply the interconnection cables when the Liebert EXM BDC is attached to the UPS 5 22...

Страница 28: ...al 1 75 44 5mm Typical All Busbars 0 56 14mm Typical 0 56 14mm Typical 0 56 14mm Typical System Input Bus See Detail B DETAIL A DETAIL B Iso View Front Left Corner Post Removed Input Output Bus Typica...

Страница 29: ...For seismic mounting only 5 102mm in rear for mounting brackets 3 Keep cabinet within 15 degrees of vertical 4 Top and bottom cable entry available through removable access plates Remove punch to sui...

Страница 30: ...punch to suit conduit size and replace 5 Control wiring and power wiring must be run in separate conduits 6 All wiring is to be in accordance with national and local electrical codes Cable Entry Area...

Страница 31: ...intenance Isolation Breaker Phase A B C F UPS Output Liebert EXM BDC Maintenance Isolation Breaker Neutral G BDC Panelboard Load AC Connection Phase A B C H BDC Panelboard Load AC Connection Neutral I...

Страница 32: ...otection by Others AC Output 208V 4 Wire GND Optional 54 Pole See Note 6 System AC Input 4 Wire GND Field Supplied Wiring BATTERY NOTES 1 Install in accordance with national and local electrical codes...

Страница 33: ...otection by Others AC Output 208V 4 Wire GND Local Grounding Electrode See Note 1 Optional 54 Pole See Note 5 System AC Input 3 Wire GND Field Supplied Wiring BATTERY NOTES 1 Install in accordance wit...

Страница 34: ...and grounding conductors 4 UPS system input and output cables must be run in separate conduits 5 Control wiring must be run in separate conduits 6 Optional 2 225A LDB for 60 100kVA frame only Optional...

Страница 35: ...4 Control wiring must be run in separate conduits 5 Optional 2 225A LDB for 60 100kVA frame only Optional single 225A LDB for 10 40kVA frame 6 Transformer available 208 220 480 600V input MBB BIB MIB...

Страница 36: ...ol wiring must be run in separate conduits 6 Optional 54 pole 225A for 10 40kVA frame only or optional 54 pole 400A for 60 100kVA frame only 7 Customer must supply shunt trip breaker with 120V coil 8...

Страница 37: ...separate conduits 5 Control wiring must be run in separate conduits 6 Optional 2 225A LDB for 60 100kVA frame only 7 Customer must supply shunt trip breaker with 120V coil 8 Remove bypass jumper busba...

Страница 38: ...Conformities UL 1778 5th Ed CSA 22 2 107 3 14 FCC Part 15 Class A ISTA Procedure 1H WEEE IBC 2012 CBC 2010 Environmental Storage Temperature Range F C 13 F to 158 F 25 C to 70 C Operating Temperature...

Страница 39: ...Black Protection Degree IEC 60529 IP20 finger proof with front doors open or closed Table 9 Liebert EXM BDC heat dissipation Liebert EXM BDC Rating kVA Liebert EXM BDC Heat Dissipation 208 208 Transf...

Страница 40: ...3W N G 175 230 1 4 0 2 1 0 M12 208 120 220 127 60 205 3W N G 300 400 2 3 0 2 4 0 M12 208 120 220 127 80 273 3W N G 350 460 2 4 0 2 300kcmil M12 208 120 220 127 100 341 3W N G 450 610 2 350kcmil 2 400k...

Страница 41: ...120 220 127 80 222 350 3W N G 400 2 3 0 2 4 0 M12 208 120 220 127 100 278 450 3W N G 460 2 4 0 2 300 kcmil M12 Refer to Figures 26 and27 for additional details about this system configuration Table 13...

Страница 42: ...811BE 1AWG 54857BE 1 0AWG 256 30695 593 2 0AWG 54862BE 60238 3 0AWG 54864BE 60244 4 0AWG 54866BE 60250 250kcmil 54868BE 60256 300kcmil 54870BE 60262 350kcmil 54872BE 60267 400kcmil 54874BE 60269 500kc...

Страница 43: ...age 40 Table 19 Electrical data Liebert EXM BDC 600VAC input 208VAC output single input with 600V 208V transformer Liebert EXM BDC Rating kVA Maximum System Input Current A Phase Recommended Upstream...

Страница 44: ...rrent protection is based on 80 rated devices and maximum input current limit setting 4 Recommended AC output external overcurrent protection is based on 80 rated devices and full rated output current...

Страница 45: ...Vertiv Liebert EXM BDC User Manual Rev 3 01 18 41 Notes...

Страница 46: ...Vertiv Liebert EXM BDC User Manual Rev 3 01 18 42...

Страница 47: ...800 543 2378 Outside North America 614 841 6598 LOCATIONS United States 1050 Dearborn Drive P O Box 29186 Columbus OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco...

Страница 48: ...es and logos referred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Co assum...

Отзывы: