Vertiv
|
Liebert
®
EXM
™
BDC User Manual | Rev. 3 | 01/18 |
27
Figure 21
Liebert EXM BDC transformer location
See
Figure 4
and
Table 1
for additional details.
Table 4
Wiring for Liebert EXM to Liebert EXM BDC
Run
From
To
Conductors
A
Utility AC source
BDC System Input Bus
Phase A, B, C
B
Utility AC Source
BDC System Input Bus
Neutral
C
BDC Bypass Isolation Breaker
UPS Main Input
Phase A, B, C
D
BDC Bypass Isolation Breaker
UPS Main Input
Neutral
E
UPS Output
Liebert EXM BDC Maintenance Isolation Breaker
Phase A, B, C
F
UPS Output
Liebert EXM BDC Maintenance Isolation Breaker
Neutral
G
BDC Panelboard
Load AC Connection
Phase A, B, C
H
BDC Panelboard
Load AC Connection
Neutral
I
Utility AC Source
All Ground Connections
Ground
J
BDC Terminal Block TB1
UPS Static Bypass Module J23, J24 and J26
Wiring for KO on Liebert EXM BDC
NOTE
Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Vertiv when the
Liebert EXM BDC and Liebert EXM UPS are ordered as a system.
Table 5
Hardware torque values
Hardware
Two Belleville Washers
M10 (3/8")
240 lb-in. (27 Nm)
M12 (1/2")
428 lb-in (48Nm)
Transformer
REAR OF CABINET
RIGHT SIDE