BDC User Manual | Rev. 3 | 01/18 |
40
Notes on Tables 18 through20.
1.
Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input
current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are
defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices.
*The recommended overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215.
2.
Maximum input current is controlled by the current limit setting.
3.
Recommended AC input external overcurrent protection is based on 80% rated devices and maximum input current limit
setting.
4.
Recommended AC output external overcurrent protection is based on 80% rated devices and full rated output current.
5.
Nominal battery voltage is shown at 2 volts per cell.
6.
Input power factor of 0.99 is used for the calculations.
40
141
3W + G
200
230
(1) 4/0
(1) 300 kcmil
M12
60
211
3W + G
300
335
(1) 400 kcmil
(2) 4/0
M12
80
281
3W + G
400
460
(2) 4/0
(2) 300 kcmil
M12
100
352
3W + G
450
510
(2) 250 kcmil
(2) 400 kcmil
M12
See
Notes on Tables 18 through20.
below.
Table 20
Electrical data—Liebert EXM BDC, 208VAC or 220VAC input, single input, with 208V:208V or 220V:220V
transformer
Liebert EXM
BDC Rating, kVA
Maximum System
Input Current, A
Phase
Recommended
Upstream
Protection, A
75°C Wire
Current, A, Total
Copper Wire
Aluminum
Wire
Bolt Size