Redundant Alarm Set:
Sets Alarm to notify
user when redundancy is no longer available.
UPS Test:
Allows user to test the Batteries,
LED’s, LCD, or Alarm.
Service Contact:
Set a contact for the user to
reach if problems occur.
Remote Shutdown:
Enables / Disables the
Remote Communications Shutdown.
If you are using SiteNet™ software, this
parameter should be enabled in order for the
UPS output to be turned off once the operating
system has been shutdown.
External Battery:
Sets total amp-hour for
external batteries to provide a more accurate
runtime remaining value on the LCD display and
through communications.
Enter in the following when using the External
Battery Cabinets with Chargers.
(P/N: PB10SLF105WC120)
# Cabinets
AH Value
1
0105
2
0210
3
0315
4
0420
5
0525
6
0630