INSTALLER’S SETTING OPTIONS
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
Select remote controller Celsius control unit setting code value ‘13’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
In value1, use ‘
▲
’, ‘
▼
’ button to select ventilation single humidification setting value, and
press ‘Done’ button to complete the setting.
- If you do not press ‘Done’ button, the setting value will not be applied.
Humidification of Stand-alone Ventilation mode (General, DX type ventilator)
It is the function to set whether to use the humidification function during the ventilation product
single operation.
h
Ventilation single humidification setting value
- 00:function not used
- 01:function used
h
If there is no button input for about 60 seconds after the setting, it automatically exits from the
setting mode.
INSTALLER’S SETTING OPTIONS
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
Select remote controller Celsius control unit setting code value ‘06’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
In value1, use ‘
▲
’, ‘
▼
’ button to select express ventilation priority setting value, and press ‘Fin-
ish’ button to complete the setting.
- If you do not press ‘Finish’ button, the setting value will not be applied.
Express ventilation priority (General, DX type ventilator)
It is the function to set the priority of the air supply and air discharge during the express ventila-
tion operation.
h
Express ventilation priority setting value
- 01: priority in air supply
- 02: priority in air discharge
h
If there is no button input for about 60 seconds after the setting, it automatically exits from the
setting mode.