Design and installation
4. Water Control
4.1 Water quality
Water quality should be complied with EN 98/83 EC Directives.
CAUTION
• If the product is installed at existing hydraulic water loop, it is important to clean hydraulic pipes to remove sludge
and scale.
• Installing sludge strainer in the water loop is very important to prevent performance degrade.
• Chemical treatment to prevent rust should be performed by installer.
• It is strongly recommended to install an additional filter on the heating water circuit. Especially to remove metallic
particles from the heating piping, it is advised to use a magnetic or cyclone filter, which can remove small
particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump
system.
• Water quality check should be implemented before completing the installation of system.
Detailed guide can be found in the table as below.
Water contents
Value
pH
7.5~9.0
Conductivity
10~500 uS/cm
TDS (Total dissolved solids)
8~400 ppm
Alkalinity (HCO
3
-
)
60~300 (mg/L)
Total hardness
4 ~ 8.5 ºdH
71.4 ~ 151.7 (mg/L)
Iron (Fe)
≤
0.2 (mg/L)
Sulphate (SO
4
2-
)
≤
100 (mg/L)
Nitrite (NO
3
-
)
≤
100 (mg/L)
Free chlorine (Cl
2
)
≤
1 (mg/L)
Chlorides (Cl
-
)
ppm
STS316
STS304
pH7
15
℃
3,000
180
40
℃
500
50
60
℃
200
30
80
℃
125
20
pH9
15
℃
18,000
700
40
℃
2,600
250
60
℃
1,000
170
80
℃
550
130
Содержание THERMAV ZHBW056A1
Страница 1: ...Air to Water Heat Pump Monobloc R32 50Hz 5BPM5 01C Replaces 5BPM5 01B P No MFL66101126 ...
Страница 2: ...THERMA V Monobloc Type General Information Product Data Design and installation ...
Страница 3: ...General Information THERMA V Monobloc Type 1 Model Line Up 2 Nomenclature ...
Страница 21: ...3 Dimensions 15 THERMA V Monobloc Type Product Data Backup Heater P No TAY37568301 ...