2. Specification
11
THERMA V
Monobloc Type
Product Data
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound power level is measured on the rated condition in the accordance with ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
Rated sound power level is according to the EN12102-1 under conditions of the EN14825
4. Performances are accordance with EN14511 and reflect ErP testing conditions. Above gives the declared values at rated conditions acc. ErP regulation.
For max. capacities, refer to Performance Data.
• Rated running current : Outdoor Temp. 7°CDB / 6°CWB, LWT 35
℃
5. This product contains Fluorinated greenhouse gases.
* DHW 58~80
℃
Operating is available only when the booster heater is operating.
Technical Specifications (Water side)
ZHBW128A1
[HM123MR U34]
ZHBW148A1
[HM143MR U34]
ZHBW168A1
[HM163MR U34]
Operation Range
(Leaving Water Temp.)
Cooling
Min. ~ Max.
°C
5 ~ 27
5 ~ 27
5 ~ 27
Heating
Min. ~ Max.
°C
15 ~ 65
15 ~ 65
15 ~ 65
DHW *
Min. ~ Max.
°C
15 ~ 80
15 ~ 80
15 ~ 80
Water Pump
Type
-
Canned type for hot water circulation
Model
-
UPML 20-105 CHBL
Motor Type
-
BLDC
Steps of Pumping Performance
-
Variable speed 10% to 100%
Power input
Min. / Rated
W
3.5 / 140
3.5 / 140
3.5 / 140
Water Flow Rate
Min. / Rated
ℓ
/min
5.0 / 46.0
5.0 / 46.0
5.0 / 46.0
Heat Exchanger
Type
-
Brazed Plate HEX
Quantity
-
1
1
1
Number of Plate
EA
76
76
76
Water Volume
ℓ
1.0
1.0
1.0
Water Flow Rate
Min. / Rated
ℓ
/min
13 ~ 70
13 ~ 70
13 ~ 70
Expansion Vessel
Volume
Max.
ℓ
8
8
8
Water pressure
Max.
bar
3
3
3
Pre-charged
bar
1
1
1
Flow Sensor
Model
SIKA VVXC9SNBUC00252P
Measuring range
Min. ~ Max.
ℓ
/min
5~80
5~80
5~80
Flow (Trigger
point)
Min.
ℓ
/min
15
15
15
Water Pressure sensor
Model
Sensata OFM(2HMP)
Measuring range Min. ~ Max.
bar(G)
0~20
0~20
0~20
Piping Connections
Inlet
inch
Male PT 1" according to ISO 7-1 (tapered pipe threads)
Outlet
inch
Male PT 1" according to ISO 7-1 (tapered pipe threads)
Strainer
Mesh size
-
30 mesh
30 mesh
30 mesh
Max. particle size
mm
0.6
0.6
0.6
Material
-
Stainless Steel
Relief Valve
Pressure Limit
Upper Limit
bar
3.0
3.0
3.0
Devices for Water Circuit
-
Relief valve / Flow Sensor
-
Drain hose
-
Pressure Sensor / Air vent
Technical Specifications (Refrigerant side)
ZHBW128A1
[HM123MR U34]
ZHBW148A1
[HM143MR U34]
ZHBW168A1
[HM163MR U34]
Operation Range
(Outdoor Temp.)
Cooling
Min. ~ Max.
°C DB
5 ~ 48
5 ~ 48
5 ~ 48
Heating
Min. ~ Max.
°C DB
-25 ~ 35
-25 ~ 35
-25 ~ 35
Compressor
Type
-
Hermetic Sealed Scroll
Model
Model × No.
RJB036MAA × 1
Motor Type
-
BLDC
Displacement
cm³/Rev.
31.6
31.6
31.6
Refrigerant
Type
-
R32
R32
R32
GWP
(Global Warming Potential)
-
675.0
675.0
675.0
Precharged Amount
g
2,000
2,000
2,000
t-CO2 eq.
-
1.350
1.350
1.350
Control
-
Electronic Expansion Valve
Refrigerant Oil
Type
-
FW68D
Charged Volume
cc × No.
1,100
1,100
1,100
Heat Exchanger
Type
Fin & Tube
Fin & Tube
Fin & Tube
Quantity
2
2
2
Specification
Row
EA
32
32
32
Column
EA
2
2
2
FPI
EA
18
18
18
Fan
Type
-
Propeller
Air Flow Rate
Rated
m³/min × No.
60.0 × 2
60.0 × 2
60.0 × 2
Fan Motor
Type
-
BLDC
Output
W × No.
124 × 2
124 × 2
124 × 2
Содержание THERMAV ZHBW056A1
Страница 1: ...Air to Water Heat Pump Monobloc R32 50Hz 5BPM5 01C Replaces 5BPM5 01B P No MFL66101126 ...
Страница 2: ...THERMA V Monobloc Type General Information Product Data Design and installation ...
Страница 3: ...General Information THERMA V Monobloc Type 1 Model Line Up 2 Nomenclature ...
Страница 21: ...3 Dimensions 15 THERMA V Monobloc Type Product Data Backup Heater P No TAY37568301 ...