7. Electric Characteristics
25
THERMA V
Monobloc Type
Product Data
Outdoor Unit
Phase / Volts / Hz
Voltage range
ZHBW056A1 [HM051MR U44]
1 Ø / 220-240 V / 50 Hz
Min. : 198
Max. : 264
ZHBW076A1 [HM071MR U44]
ZHBW096A1 [HM091MR U44]
ZHBW126A1 [HM121MR U34]
1 Ø / 220-240 V / 50 Hz
ZHBW146A1 [HM141MR U34]
ZHBW166A1 [HM161MR U34]
ZHBW128A1 [HM123MR U34]
3 Ø / 380-415 V / 50 Hz
Min. : 342
Max. : 457
ZHBW148A1 [HM143MR U34]
ZHBW168A1 [HM163MR U34]
Backup Heater
Power Supply for Heater
Phase / Volts / Hz
Capacity (kW)
AHEH036A [HA031M E1]
1 Ø / 220-240 V / 50 Hz
3
AHEH066A [HA061M E1]
3+3
AHEH068A [HA063M E1]
3 Ø / 380-415 V / 50 Hz
2+2+2
DHW Boost Heater
Power Supply for DHW Boost Heater
Phase / Volts / Hz
Capacity (kW)
Integral part of DHW tanks [OSHW-x00F(D)]
1 Ø / 220-240 V / 50 Hz
2.4
[Power Supply for Heat pump, Backup heater and DHW boost heater]
Note
1.Voltage supplied to the unit terminals should be within the minimum and maximum range.
2.Maximum allowable voltage unbalance between phase is 2%.
a
&%
(/&%
'+:
7DQN
%DFNXS
+HDWHU
6ZLWFK
%R[
&%
&%
Sensor
'+:
7DQNNLW
Signal
Power source
8QLW
Contact Signal
Live Signal
for DHW Tank kit
Содержание THERMAV ZHBW056A1
Страница 1: ...Air to Water Heat Pump Monobloc R32 50Hz 5BPM5 01C Replaces 5BPM5 01B P No MFL66101126 ...
Страница 2: ...THERMA V Monobloc Type General Information Product Data Design and installation ...
Страница 3: ...General Information THERMA V Monobloc Type 1 Model Line Up 2 Nomenclature ...
Страница 21: ...3 Dimensions 15 THERMA V Monobloc Type Product Data Backup Heater P No TAY37568301 ...