- 65 -
Operation & Maintenance Manual
n
Maintenance
Maintenance/Repair schedule
Checkpoint
Daily
Monthly
Every 2
months
Every 3
months
Every 6
months
Every
1 year
Every 2
years
Every 3
years
Every 6
years
10 h
500 h
1000 h
1500 h
2500 h
5000 h
10000 h
15000 h
30000 h
1. Cycle condition
Check
2. Electric part
Check
-
-
-
-
-
Monthly check
3. Safety switch
Check
Monthly check
4.
Check
-
Check
-
-
-
-
-
-
-
-
Check every 6 months
5.
Check every 6 months. When the
operating pressure of the cooler is out of
the range, clean the unit.
6.
Check
Check
Annual clean
7.
Check
-
Check
Monthly check
8. Oil filter
Check
Check
-
-
-
Check every 6 months. Clean if necessary.
9. Dryer filter
Check
Annual replacement
10. Oil amount
Check
Annual check
11. Oil color
Check
Replace
Replace
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
12.
Check
Annual check
13.
Check
Check every 6 months
14.
Check
Check or
replace
Cold water,
Coolant water
circulation system
Evaporator,
Condenser
cleanness
Cooling tower
cleanness
Cooling system
leakage
Compressor
insulation
Temperature
sensor
Compressor
bearing
Table 23
Содержание RCWW-1
Страница 14: ... 14 Chiller Water cooled Screw User Setting Fig 5 ...
Страница 16: ... 16 Chiller Water cooled Screw Function Setting Fig 6 ...
Страница 18: ... 18 Chiller Water cooled Screw I O Display ...
Страница 23: ... 23 Operation Maintenance Manual Running Information Fig 8 ...