Operation & Maintenance Manual
Alarm History
Last operated alarm will be indicated on Alarm display with time. Also, operator can cancel alarm on
the screen. See the Fig4 below for cancellation of alarm.
As explained in the Fig4 above, click the arrow
▽△
to move to the alarm contents which operator
wants to eliminate, and select the alarm by clicking OK. Cancel the alarm by clicking Clear.
Canceled alarm would be eliminated in the alarm display screen.
If operator does not cancel the alarm after alarm is ON, Chiller would not work even if actual alarm
situation is complete. After alarm is ON, always cancel the alarm and re-start it for operation.
Alarm elimination (Reset)
OK
Clear
Alarm elimination (Reset)
Done
Cancellation
Fig. 3
Fig. 4