58
Outdoor Unit
Test Run
Integrated Trial Run Function - Cooling Mode
Start Inspection
Press black button for 2 seconds
YES
YES
YES
NO
Suitable
Temperature Condition
Turn off thermo,
detect indoor unit
Acquisition of automatic trial run data
during entire unit operation of
refrigerant detection (15minutes)
Operation of 1 indoor unit
Acquisition of 1 unit operation data
(10minutes)
Error Display
Error Display
Press black button
for 2 seconds
End
Press black button for 2
seconds after turning off all dip
switches
Normal mode
Cooling Mode operation
of entire unit
Note 1) Please whether normal or not by referring to multi V trial run result report.
Dip Switch Configuration Method
Warning :
Make sure to reset Main PCB
before executing these functions
- It is a process to verify normal operation of the system and components attached to the system through system operation.
- It executes overall process including refrigerant detection logic then executes a process of verifying normal operation of
each component when executed in Cooling Mode.
- Secured data can be verified through LGMV