62
Outdoor Unit
Test Run
■
Noise reduction compared to Standard Cooling Mode operation [dB]
Mode
Front Rear
(Outdoor side) (Indoor side)
Quiet Operation -7 -6
It is a function to provide a contact point (220V) to connect the product and commercial auto-louver.
■
Turn on indoor unit operation mode : Turn on contact point (Main PCB CN15 terminal 220V output)
■
Turn off all indoor unit operation mode : Turn off contact point (Main PCB CN15 terminal 0V output)
■
Dip switch configuration method of usage of contact point for connection to commercial auto-louver (Reset the
power after configuring the dip switch)
Q R S T U V W
on
Q R S T U V W
on
Connection Point :
Main PCB CN15
Terminal
Providing of contact
point for connection to
commercial auto-louver
Function
SW01B
SW02B
Remarks
SW01B
(DIP S/W)
SW02B
(DIP S/W)
7 - Segment
SW02V
Auto addressing
SW01V
Data confirm
CN 15
commercial
auto-louver
Control box
for commercial
auto-louver
Switching Control
Contact Point Signal
Connection on Site l
Function to provide contact point for connection to commercial auto-louver
1. For configuration of functions, ask the installation specialist during installation of outdoor unit.
2. When not using the function, turn off the dip switch then reset the power.
3. Cooling capability may decline if RPM of outdoor unit is altered.
CAUTION
Please carry out work after familiarizing the installation manual of auto-louver when using the product in connection with
commercial auto-louver.
Please prepare and use additional components for connection suitable to site conditions.
Take precautions to selection of commercial auto-louver as it does not provide signals other than 220V contact point.
CAUTION