Test Run
Multi V Trial Run Result Report
Multi V Trial Run Result Report
Trial Run Result
Minimum Maximum Average Minimum Maximum Average Total
Person in
Charge
Date
Operation mode
Entire Unit Operation
1 Unit Operation
Stage
Inspection Item
Company Name & Address
Model
Model
No.
Installation Location
Judgment Standard
20~30°C
3600kPa
↓
(Cooling)
2300kPa
↓
(Heating)
1300kPa
↑
(Cooling)
200kPa
↑
(Heating)
24A
↓
50~100°C
18A
↓
342~456V
20A
↓
10~50°C(Heating)
0.5°C
↑
(Cooling)
0.5°C~7°C(Heating)
Telephone No.
Name
Installer
Consultant
Supervisor
Outdoor Unit
Indoor Unit
Distributor
Pressure
Voltage
Decision Standard means that when detection value deviates from this value, it can be decided as error, and in this case verifying again
with considerations for cycle is recommended.
Current
Exhaust
overheat
level
Intake
Overheat
level
EEV
Opening
Estimated Refrigerant Amount
COMP
High Pressure
Low Pressure
Comp Operation Verification
Inverter Current
Inverter 1
Inverter 2
Inverter 3
Inverte r4
Inverter 1
Inverter 2
Inverter 3
Inverter 4
Static 1
Static 2
Static 3
Static 4
Static 5
Static 6
Static 7
Static 8
Static 1
Static 2
Static 3
Static 4
Static 5
Static 6
Static 7
Static 8
Exhaust Temperature
Static Current
R-conductor
T-conductor
R-conductor
T-conductor
Outdoor Unit#1
Outdoor Unit#2
Outdoor Unit#3
Outdoor Unit#4
Outdoor Unit#1
Outdoor Unit#2
Outdoor Unit#3
Outdoor Unit#4
Outdoor Unit#1
Outdoor Unit#2
Outdoor Unit#3
Outdoor Unit#4
Product
Temperature
Indoor Temperature
Outdoor Temperature
Inlet Pipe Temperature
Outlet Pipe Temperature
EEV Opening
Indoor Unit
Outdoor
Unit
Print in the order shown below using LG MV in order to issue Multi V Trial Run Result Report.
ENGLISH