29
E
N
G
L
IS
H
CAUTION
• Request installer to set the function during installation.
• If setting the op 13,14 the cooling capacity may go down.
When high load occurs at indoor, do not use this function.
!
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn4” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on” ~ “oFF” Push the ‘
●
’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- oFF: Operate partial defrost
CAUTION
• Ask an authorized technician to setting a function.
* A(C)RUN***LLS4, A(C)RUN***LLN4 models operate only over-
all defrost function.
!
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn5” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“0” ~ “254” Push the ‘
●
’ button
ODU address is set
CAUTION
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
!
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn6” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1” ~ “op3” Push the ‘
●
’ button
Mode is set
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an oFF-mode.
!
Mode setting
setting
Mode
oFF
Not setting
op1
Snow removal mode
op2
Rapid defrost mode
op3
Snow removal mode. + Rapid defrost mode.
RPM/ Time Settings
Noise
Reference of Cooling Capacity Table (%)
* Reducing noise by changing ODU RPM, cooling capacity may go
down. Please refer to the following table.
Capacity
Heat Pump
UX5
UX6
Step
Noise(dB)
op1~op3, op10
55
59
op4~op6, op11
52
56
op7~op9, op12
49
53
op13
55
55
op14
50
50
HP
Step
8
10
12
14
16
18
20
22
op13
100
98
87
67
60
54
48
44
op14
98
78
69
55
49
44
39
35
Step
Judgment Time (Hr)
Operation Time(Hr)
op1
8
9
op2
6.5
10.5
op3
5
12
op4
8
9
op5
6.5
10.5
op6
5
12
op7
8
9
op8
6.5
10
op9
5
12
op10
0
Continuous operation
op11
0
op12
0
op13
6.5
10.5
op14
6.5
10.5
Snow removal & rapid defrost
Mode setting method
Setting the ODU address
Mode setting method
Overall defrost mode
Mode setting method