Example) Group number setting
1
st
number indicate the group number
2
nd
number point out indoor unit number
[Cooling Only]
B(D)
A(C)
B
A
SODU.B SODU.A
IDU.B
IDU.A
CEN.B
CEN.A
DRY1
DRY2
GND
12V
B
SODU
IDU
INTERNET DRY1 DRY2 GND
12V
A
B
A
B
A
B(D)
A(C)
B
A
1 F
Group Indoor unit
Group recognizing the central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn1” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”,“op2” Push the ‘
●
’ button
Cool & Heat Selection mode is set
Function setting
Switch control
Function
Switch(Up) Switch(Down)
oFF
op1(mode)
op2(mode)
Right side (On) Left side (On) Not operate
Cooling
Cooling
Right side (On) Right side (On) Not operate
Heating
Heating
Left side (On)
-
Not operate
Fan mode
Off
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
!
Switch (Up)
Switch (Down)
Left side
Right side
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn2” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1” Push the ‘
●
’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Capacity
8~14 HP
16~22 HP
Max. RPM
Standard
730
950
op1
800
1000
op2
820
-
op3
850
-
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn3” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1~op14” Push the ‘
●
’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM
to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure
has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
Cool & Heat selector
Mode setting method
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outdoor Units (External PCB)